10 GENERAL INFORMATION

TN, TT, IT 3+PE. 380−460V, 50Hz/60Hz.

KEY

XS1 Main terminals

QF1 Fan motor starter QF1.1 Auxiliary contact

FU3 Transformer secondary fuse FU1, 2 Transformer primary fuses

FR1 Solid state relay

FR2 Solid state relay

FR3 Solid state relay

EDV Electric drain valve

DR Variable speed drive

MMMain motor

FM Blower motor

MC Dryer motor

ES Emergency stop

1ATS High air temperature switch 1RPS Dryer refrigeration pressure switch

PTO Thermistor, motor winding temp. P1, P2 Pressure transducer

EDVO Electronic drain valve option

DO Dryer option

CA Common alarm

WHT

White

RED

Red

DDP

Dryer discharge pressure (Dryer option)

ADP

Aftercooler discharge pressure

WIRES

POWER − Black

DC CONTROL − Blue

NEUTRAL − Light blue

PROTECTIVE EARTH − Green / Yellow

NOTES

1.THE CORRECT TYPE AND RATING OF LINE INPUT FUSE MUST BE FITTED ONTO THE CUSTOMER’S ISOLATOR OR BREAKER CLOSE TO THE COMPRESSOR.

FAST ACTING CLASS−J, T OR SEMICONDUCTOR TYPE, CURRENT LIMITING, INTERRUPT RATING − 200,000 AMPS RMS

SECTION

2.SIZING OF ELECTRICAL COMPONENTS NOT SUPPLIED BY INGERSOLL RAND IS THE RESPONSIBILITY OF THE CUSTOMER AND SHOULD BE DONE IN ACCORDANCE WITH THE INFORMATION ON THE COMPRESSOR DATA PLATE, N.E.C., AND LOCAL ELECTRICAL CODES.

3.DECAL MUST CONFORM TO THE LATEST REVISION OF IR SPECIFICATION 92−8.95.

en

http://air.ingersollrand.com

Page 12
Image 12
Ingersoll-Rand 80445364 manual General Information