INSTALLATION / HANDLING

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ELECTRICAL DATA − ALL UNITS IRN 30HP / 22kW

 

 

 

 

 

 

 

 

 

 

 

 

Standard voltage

 

Low Voltage

 

High Voltage

 

 

 

 

 

 

 

 

 

 

 

 

 

208V

 

230V

380V

400V

460V

 

 

 

 

 

 

 

 

 

 

Drive motor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Motor enclosure

 

 

 

IP65

 

 

 

 

 

 

 

 

 

 

 

 

Power

 

 

 

 

20HP / 15kW

 

 

 

 

 

 

 

 

 

 

Full load current (maximum)

91

 

82

50

47

41

 

 

 

 

 

 

 

 

 

Starts per hour (maximum)

 

 

 

20

 

 

 

 

 

 

 

 

 

 

 

ELECTRICAL DATA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Control voltage

 

 

 

 

24VDC

 

 

 

 

 

 

 

 

 

 

 

Maximum fuse rating

150A

 

125A

75A

75A

70A

 

See note 1, 3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Minimum wire size AWG

 

 

 

 

 

 

 

(mm2)

 

2 (32)

 

2 (32)

6 (16)

6 (16)

6 (16)

 

See note 2, 3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ELECTRICAL DATA − ALL UNITS IRN 40HP / 30kW

 

 

 

 

 

 

 

 

 

 

 

Standard voltage

 

Low Voltage

 

High Voltage

 

 

 

 

 

 

 

 

 

 

 

 

 

208V

 

230V

380V

400V

460V

 

 

 

 

 

 

 

 

 

 

Drive motor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Motor enclosure

 

 

 

IP65

 

 

 

 

 

 

 

 

 

 

 

 

Power

 

 

 

 

25HP / 18.5kW

 

 

 

 

 

 

 

 

 

 

 

Full load current (maximum)

122A

 

110A

66.5A

63A

55A

 

 

 

 

 

 

 

 

 

Starts per hour (maximum)

 

 

 

20

 

 

 

 

 

 

 

 

 

 

 

ELECTRICAL DATA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Control voltage

 

 

 

 

24VDC

 

 

 

 

 

 

 

 

 

 

 

Maximum fuse rating

200A

 

200A

125A

100A

80A

 

See note 1, 3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Minimum wire size AWG

 

 

 

 

 

 

 

(mm2)

 

2/0 (70)

 

2/0 (70)

4 (25)

4 (25)

4 (25)

 

See note 2, 3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.The correct type and rating of line input fuse MUST BE fitted onto the customers isolator or breaker close to the compressor.

Fast Acting Class−J, T or Semiconductor type, Current limiting, Interrupt Rating − 200,000 Amps RMS SYM.

Alternate fuse may be used if the time current characteristics are faster than fuses recommended in this section.

2. PVC/PVC Type Calculated using the following conditions:

i)PVC insulated cable, armoured, copper conductors.

ii)Cable clipped to a wall, in free air.

iii)Ambient temperature of 40_C (104_F) and relative humidity of 40%.

iv)20m (65ft) cable run.

v)Volt drop limited to −10% during starting, −4% during normal running.

vi)Protected by the fuse listed above.

3.Always apply local electrical codes for sizing cables and fusing.

If there are any deviations from the above, or special regulations apply, the installation must be planned by a competent, qualified engineer.

NOTE

All data applies to standard product only.

en