5.1.1Service Schedule, 14RESA/RESAL Models
|
|
|
|
| Procedure |
|
|
| |
|
|
|
|
|
|
|
|
| |
|
| See | Visually |
|
|
|
|
| |
System Component or Procedure |
| Section | Inspect | Check | Change | Clean | Test | Frequency | |
Fuel |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Flexible lines and connections |
|
|
| X |
| R |
|
| Quarterly |
|
|
|
|
|
|
|
|
|
|
Main tank supply level |
|
|
|
| X |
|
|
| Weekly |
|
|
|
|
|
|
|
|
|
|
Fuel piping |
|
|
| X |
|
|
|
| Yearly |
|
|
|
|
|
|
|
|
|
|
Lubrication |
| 5.2 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Oil level |
|
|
| X | X |
|
|
| 8 hours or |
|
|
|
|
|
|
| before use | ||
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
Crankcase breather hose |
|
|
| X |
|
|
|
| Yearly or 500 hours |
|
|
|
|
|
|
|
|
|
|
Change oil |
|
|
|
|
| X |
|
| Yearly or 100 hours |
|
|
|
|
|
|
|
|
|
|
Replace filter |
|
|
|
|
| X |
|
| Yearly or 200 hours |
|
|
|
|
|
|
|
|
|
|
Cooling |
| 5.5 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Air ducts, louvers |
|
|
|
| X |
| X |
| Yearly |
|
|
|
|
|
|
|
|
|
|
Exhaust Line |
| 5.6 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Leakage |
|
|
| X | X |
|
|
| Weekly |
|
|
|
|
|
|
|
|
|
|
Insulation, fire hazards |
|
|
| X |
|
|
|
| Yearly |
|
|
|
|
|
|
|
|
|
|
Obstructions or combustible materials near exhaust |
|
|
| X |
|
|
|
| Weekly |
outlet |
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
DC Electrical System |
| 5.7 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Battery charger operation, charge rate (if equipped) |
|
|
| X |
|
|
|
| Monthly |
|
|
|
|
|
|
|
|
|
|
Remove corrosion, clean and dry battery and rack |
|
|
| X |
|
| X |
| Yearly |
|
|
|
|
|
|
|
|
|
|
Clean and tighten battery terminals and inspect |
|
|
| X | X |
|
|
| Yearly |
boots |
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
Battery electrolyte level and specific gravity * |
|
|
|
| X |
|
|
| Yearly |
|
|
|
|
|
|
|
|
|
|
AC Electrical System |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Tighten control and power wiring connections |
|
|
|
| X |
|
|
| Yearly |
|
|
|
|
|
|
|
|
|
|
Remote control system, if equipped |
|
|
|
|
|
|
| X | Monthly |
|
|
|
|
|
|
|
|
|
|
Visible wear or damage |
|
|
| X |
|
|
|
| Quarterly |
|
|
|
|
|
|
|
|
|
|
Wire abrasions where subject to motion |
|
|
| X | X |
|
|
| Six Months |
|
|
|
|
|
|
|
|
|
|
|
|
| X |
|
|
|
| 3 Years or 500 hours | |
|
|
|
|
|
|
|
|
|
|
Engine and Mounting |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Visible wear or damage |
|
|
| X |
|
|
|
| Weekly |
|
|
|
|
|
|
|
|
|
|
Air cleaner and precleaner service [ |
| 5.4 |
|
|
| R |
|
| Yearly or 100 hours |
|
|
|
|
|
|
|
|
|
|
Spark plugs |
| 5.3 |
|
|
| X |
|
| Yearly or 300 hours |
|
|
|
|
|
|
|
|
|
|
Replace stepper motor coupling and bushing |
|
|
|
|
| D |
|
| 500 hours |
|
|
|
|
|
|
|
|
|
|
Generator |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Visible wear or damage |
|
|
| X |
|
|
|
| Quarterly |
|
|
|
|
|
|
|
|
|
|
Exercise generator set |
|
|
|
|
|
|
| X | Weekly |
|
|
|
|
|
|
|
|
|
|
Brushes and collector ring |
|
|
| D |
|
| D |
| Yearly |
|
|
|
|
|
|
|
|
|
|
Measure and record resistance readings of |
|
|
|
|
|
|
|
|
|
windings with insulation tester (Meggerr, with |
|
|
|
|
|
|
| D | 3 Years |
SCR assembly or rectifier and load leads |
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
| |
disconnected) * |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
General Condition of Equipment |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Evidence of vibration, leakage, excessive noise, |
|
|
| X | X |
| X |
| Weekly |
temperature, or deterioration |
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
Interior of sound enclosure |
|
|
| X |
|
| X |
| Quarterly |
|
|
|
|
|
|
|
|
|
|
* Not necessary for |
| X | Action |
|
|
|
|
| |
[ Service more frequently under extremely dusty/dirty conditions. | D | Authorized distributor/dealer only |
| ||||||
Meggerr is a registered trademark of Biddle Instruments. |
| R | Replace as necessary |
|
|
| |||
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
58 Section 5 Scheduled Maintenance |