5.1.2Service Schedule, 20RESA/RESAL Models
|
|
|
| Procedure |
| |||
|
|
|
|
|
|
|
|
|
| See | Visually |
|
|
|
|
|
|
System Component or Procedure | Section | Inspect | Check | Change | Clean | Test | Frequency | |
Fuel |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Flexible lines and connections |
| X |
|
| R |
|
| Quarterly |
|
|
|
|
|
|
|
|
|
Main tank supply level |
|
|
| X |
|
|
| Weekly |
|
|
|
|
|
|
|
|
|
Fuel piping |
| X |
|
|
|
|
| Yearly |
|
|
|
|
|
|
|
|
|
Lubrication | 5.2 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Oil level |
|
|
| X |
|
|
| 8 hours or |
|
|
|
|
|
|
|
| before each use |
|
|
|
|
|
|
|
|
|
Change oil |
|
|
|
| X |
|
| Yearly or 150 hours |
|
|
|
|
|
|
|
|
|
Replace filter |
|
|
|
| X |
|
| Yearly or 150 hours |
|
|
|
|
|
|
|
|
|
Crankcase breather hose |
| X |
|
|
|
|
| Yearly or 500 hours |
|
|
|
|
|
|
|
|
|
Oil cooler |
| X |
|
|
| X |
| Yearly or 100 hours |
|
|
|
|
|
|
|
|
|
Cooling | 5.5 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Air ducts, louvers |
|
|
| X |
| X |
| Yearly |
|
|
|
|
|
|
|
|
|
Exhaust System | 5.6 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Leakage |
| X |
| X |
|
|
| Weekly |
|
|
|
|
|
|
|
|
|
Insulation, fire hazards |
| X |
|
|
|
|
| Yearly |
|
|
|
|
|
|
|
|
|
Obstructions or combustible materials near |
| X |
|
|
|
|
| Weekly |
exhaust outlet |
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
DC Electrical System | 5.7 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Battery charger operation, charge rate |
| X |
|
|
|
|
| Monthly |
|
|
|
|
|
|
|
|
|
Remove corrosion, clean and dry battery and |
| X |
|
|
| X |
| Yearly |
rack |
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
Clean and tighten battery terminals and inspect |
| X |
| X |
|
|
| Yearly |
boots |
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
Battery electrolyte level and specific gravity * |
|
|
| X |
|
|
| Yearly |
|
|
|
|
|
|
|
|
|
AC Electrical System |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Tighten control and power wiring connections |
|
|
| X |
|
|
| Yearly |
|
|
|
|
|
|
|
|
|
Remote control system, if equipped |
|
|
|
|
|
| X | Monthly |
|
|
|
|
|
|
|
|
|
Visible wear or damage |
| X |
|
|
|
|
| Quarterly |
|
|
|
|
|
|
|
|
|
Wire abrasions where subject to motion |
| X |
| X |
|
|
| Six Months |
|
|
|
|
|
|
|
|
|
| X |
|
|
|
|
| 3 Years or 500 hours | |
|
|
|
|
|
|
|
|
|
Engine and Mounting |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Visible wear or damage |
| X |
|
|
|
|
| Weekly |
|
|
|
|
|
|
|
|
|
Air cleaner service [ | 5.4 |
|
| 150 | 300 |
|
| Yearly or hours shown |
|
|
|
|
|
|
|
|
|
Spark plugs | 5.3 |
|
| 150 | 300 |
|
| Yearly or hours shown |
|
|
|
|
|
|
|
|
|
Replace stepper motor coupling and bushing |
|
|
|
| D |
|
| 500 hours |
|
|
|
|
|
|
|
|
|
Generator |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Visible wear or damage |
| X |
|
|
|
|
| Quarterly |
|
|
|
|
|
|
|
|
|
Exercise generator set |
|
|
|
|
|
| W | Weekly |
|
|
|
|
|
|
|
|
|
Brushes and collector ring |
| D |
|
|
| D |
| Yearly |
|
|
|
|
|
|
|
|
|
Measure and record resistance readings of |
|
|
|
|
|
|
|
|
windings with insulation tester (Meggerr, with |
|
|
|
|
|
| D | 3 Years |
SCR assembly or rectifier and load leads |
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| |
disconnected) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
General Condition of Equipment |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Evidence of vibration, leakage, deterioration, |
| X |
| X |
| X |
| Weekly |
unusual or excessive noise or temperature |
|
|
|
| ||||
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
Interior of sound enclosure |
| X |
|
|
| X |
| Quarterly |
|
|
|
|
|
|
|
|
|
* Not necessary for |
|
| X | Action |
| |||
[ Service more frequently under extremely dusty/dirty conditions. | D | Authorized distributor/dealer only |
| |||||
Meggerr is a registered trademark of Biddle Instruments. |
| R | Replace as necessary |
| ||||
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
Section 5 Scheduled Maintenance 59 |