| Air Pressure Switch | Check for 120 VAC on both sides of switch. If |
|
| voltage present on one side only, check for air tube |
|
| blockage. Adjust air switch. If above fails, replace |
|
| air pressure switch. |
| Transformer, 24 VAC | Check for 120 VAC to primary of transformer. |
|
| Check for 24 VAC from secondary of transformer. If |
|
| there is primary voltage, but no secondary voltage, |
|
| replace transformer. |
NOTE: | (Model 1004 & 1005) | For oven models 1004 and 1005, there is a 1 Amp |
|
| fuse located between the 24 VAC output from the |
|
| transformer and the coil of the burner motor relay. If |
|
| there is 24 VAC output from the transformer, but no |
|
| burner motor relay action, check fuse and fuse |
|
| holder. Replace as necessary. |
| Burner Motor Relay | Delete burner motor relay refer to Section D, Page |
|
| 34. |
| Burner Blower Motor | Check for 120 VAC supply to burner blower motor. |
|
| If 120 VAC is present and motor does not run, |
|
| replace motor. WITH POWER OFF: turn blower |
|
| wheel to check for locked rotor. |
| Centrifugal Switch of Burner | Check for 24 VAC output from secondary of |
| Blower Motor | transformer. If voltage is present, check for 24 VAC |
|
| at pin 6 and the ground bar on ignition control and |
|
| valve assembly. If the burner blower motor is |
|
| running and there is no voltage at pin 6 and the |
|
| ground bar on the ignition control valve, replace the |
|
| burner blower motor. |
For ovens with | Ignition Control and Valve | Check for 24 VAC supply to the ignition control and |
Johnson Controls | Assembly | valve assembly at pin 6 and the ground bar. If |
Ignition Control |
| voltage is present, check for 24 VAC across pin #1 |
(For ovens with |
| and the ground bar (pilot valve). If voltage is not |
| present, replace electronic control package. If the | |
Honeywell Ignition |
| pilot valve is energized, check to see that the high |
control, See Pg. 21) |
| voltage ignitor circuit is also energized. To check, |
|
| disconnect the ignitor lead from the bottom of |
|
| ignition control. Place female terminal of ignitor |
|
| lead approximately 1/8" from terminal post on |
|
| ignition control. Spark should jump the 1/8" gap. If |
|
| no spark is present, replace ignition control. |
| No Pilot | If the ignition control is supplied with 24 VAC, and |
|
| the pilot valve (internal to valve assembly) and |
|
| ignitor circuits are energized, visually check for pilot |
|
| flame. This may be done by opening the small |
|
| inspection door on the end of the burner, or by |
|
| opening the main oven door and looking under the |
|
| lower finger housings on the right side of the oven. |
|
| If no pilot flame is visible, check the following. |
| Pilot | Check to see that pilot |
|
| off valve is located between ignition control and |
|
| valve assembly and burner.) |
| Pilot Tube | Check for gas pressure at pilot tube. Disconnect |
|
| pilot tube at burner and connect manometer to pilot |
|
| tube. If no gas pressure is present, check for |
|
| blockage in pilot tube or pilot |
|
| are clear, and there is gas supplied to the oven, |
|
| replace the ignition control and valve assembly. |
| Pilot Orifice | If there is gas pressure at the pilot tube, check the |
|
| pilot orifice for obstructions. Replace as need |
| Burner Ignitor | Check the burner ignitor head for any obstructions, |
|
| also check for frayed or broken wire, any type of |
|
| damage to spark gap (.100 in. 2.5 m.m.) If there is |
|
| visible damage, replace ignitor assembly. |
Impinger I | 21 |