INSTALLATION | ||
|
|
|
AUXILIARY POWER RECEPTACLES, PLUGS, AND
The control panel of the RANGER 300 features three auxiliary power receptacles: See Figure B.1.
•Two 15 amp, 120 volt duplex (double outlet) recepta- cles.
•One 50 amp 120/240 volt simplex (single outlet) receptacle.
Through these receptacles the machine can supply up to 12,000 rated continuous watts of
For further protection against electric shock, any elec- trical equipment connected to the generator recepta- cles must use a
If you need ground fault protection for
CIRCUIT BREAKERS
The RANGER 300 machines are equipped with 50 amp circuit breakers on the 120/240 V receptacle and 15 amp circuit breakers on the 120 receptacles for overload protection. Under high heat a breaker may tend to trip at lower loads than it would normally.
CAUTION
Never bypass the circuit breakers. Without overload protection, the RANGER 300 D/DLX could overheat and/or cause damage to the equipment being used.
PREMISES WIRING
The RANGER 300 is suitable for temporary, standby, or emergency power using the engine manufacturer’s recommended maintenance schedule. With its three- wire grounded neutral generator, it can be permanent- ly installed as a standby power unit for 240 volt, three wire, single phase 50 ampere service.
WARNING
Only a licensed, certified, trained electrician should install the machine to a premises or residential elec- trical system. Be certain that:
•The installation complies with the National Electrical Code and all other applicable electrical codes.
•The premises is isolated and no feedbacking into the utility system can occur. Certain state and local laws require the premises to be isolated before the generator is linked to the premises. Check your state and local requirements.
•A double pole, double throw transfer switch in con- junction with the properly rated double throw circuit breaker is connected between the generator power and the utility meter.
The following information and the connection diagram, Figure A.1, can be used as a guide by the electrician for most applications to premises wiring.
1.Install a double pole, double throw switch between the power company meter and the premises dis- connect. The switch rating must be the same as or greater than the premises disconnect and service overcurrent protection.
2.Take the necessary steps to assure that the load is limited to the capacity of the RANGER 300 by installing a 50 amp 240 volt double pole circuit breaker. Maximum rated load for the 240 volt auxil- iary is 50 amperes. Loading above 50 amperes will reduce output voltage below the allowable
3.Install a 50 amp 120/240 volt plug (NEMA type 14-
50)to a double pole circuit breaker using No. 8 or larger, 4 conductor cable of the desired length. (The 50 amp 120/240 volt plug is available in the optional power plug kit.
4.Plug this cable in to the 50 amp 120/240 volt recep- tacle on the RANGER 300 case front.
RANGER 300 D AND 300 DLX