3 General venting (continued)
6.Priming and Cementing:
a.Handle fittings and pipes carefully to prevent contamination of surfaces.
b.Apply a liberal even coat of primer to the fitting socket.
c.Apply a liberal even coat of primer to the pipe end to approximately 1/2" beyond the socket depth.
d.Apply a second primer coat to the fitting socket.
e.While primer is still wet, apply an even coat of approved cement to the pipe equal to the depth of the fitting socket.
Table 3A Vent Pipe, and Fittings
f.While primer is still wet, apply an even coat of approved cement to the fitting socket.
g.Apply a second coat of cement to the pipe.
h.While the cement is still wet, insert the pipe into the fitting, if possible twist the pipe a 1/4 turn as you insert it. NOTE: If voids are present, sufficient cement was not applied and joint could be defective.
i.Wipe excess cement from the joint removing ring or beads as it will needlessly soften the pipe.
All vent pipe materials and fittings must comply with the following:
Item | Material | Standards for installation in: | ||
United States | Canada | |||
|
| |||
| PVC Plastic Pipe, Schedules 40, 80, & 120 | ANSI/ASTM D1785 |
| |
|
|
|
| |
| PVC Plastic Pipe Fittings, Schedule 40 | ANSI/ASTM D2466 | CPVC and PVC venting must be | |
|
|
| ||
| PVC Plastic Pipe Fittings, Schedule 80 | ANSI/ASTM D2467 | ||
Vent pipe and | Certified. IPEX is an approved manufacturer | |||
fittings | PVC - DWV Pipe and Fittings | ANSI/ASTM D2665 | in Canada supplying vent material listed to | |
|
|
| ||
| CPVC Plastic Pipe, Schedule 40 & 80 | ANSI/ASTM F441 | ||
|
| |||
| CPVC Plastic Pipe Fittings, Schedule 80 | ANSI/ASTM F439 |
| |
|
|
|
| |
| UL1738 | |||
| NOTICE: DO NOT USE CELLULAR (FOAM) CORE PIPE | |||
| Approved Stainless Steel Vent Manufacturers | |||
| Make |
| Model | |
ProTech Systems (Simpson |
| FasNSeal Vent / FasNSeal Flex* Vent | ||
| ||||
Heat Fab (Selkirk Corporation) |
|
*Use of FasNSeal Flex smooth inner wall vent is to be used in vertical or near vertical sections only, taking precaution to ensure no sagging occurs of the vent system. Connect to the FasNSeal rigid vent using specially designed adapters and sealing method, see manufacturer’s instructions.
PVC/CPVC Air intake/vent connections
1.Combustion Air Intake Connector (FIG.’s
2.Vent Connector (FIG.’s
Figure
AIR
VENT
3” CPVC PIPE SUPPLIED WITH WATER HEATER MUST BE USED FOR VENT CONNECTION
NOTE: CPVC VENT PIPE AND VENT FITTINGS MUST BE USED IN CLOSET AND ALCOVE INSTALLATIONS.
Figure
AIR
VENT
4" CPVC PIPE SUPPLIED WITH WATER HEATER MUST BE USED FOR VENT CONNECTION
NOTE: CPVC VENT PIPE AND VENT FITTINGS MUST BE USED |
| 19 |
| ||
IN CLOSET AND ALCOVE INSTALLATIONS. |
|
|