Lochinvar 151 Number of Units, Model, Required Pipe Sizes in NPT, Cold Water, Supply, Return

Models: 151

1 76
Download 76 pages 1.76 Kb
Page 42
Image 42
Figure 6-7Double Heater - Single Tank

Installation & Operation Manual

6 System piping

Figure 6-7Double Heater - Single Tank

 

 

 

Number of Units

 

 

Model

2

3

4

5

6

7

8

 

 

Required Pipe Sizes in NPT

 

151

1 1/2"

2"

2"

2"

2 1/2"

3"

3"

200

1 1/2"

2"

2 1/2"

2 1/2"

3"

3"

4"

286

2"

2 1/2"

2 1/2"

3"

3"

4"

4"

400

2 1/2"

3"

3 1/2"

4"

4"

5"

5"

501

3"

3 1/2"

4"

5"

5"

5"

6"

601

3"

3 1/2"

4"

5"

5"

5"

6"

701

3"

4"

5"

5"

6"

6"

6"

801

3"

4"

5"

6"

6"

6"

6"

COLD WATER

EXPANSION

SUPPLY

TANK

FLOW CHECK

 

VALVE (TYPICAL)

 

BUILDING

 

RETURN

 

HOT WATER

MIXING

SUPPLY

VALVE

THERMOMETER

 

TEMPERATURE

 

& PRESSURE

 

RELIEF VALVE

 

WATER HEATER

CIRCULATOR

(TYPICAL)WATER

HEATER (TYPICAL)

UNION (TYPICAL)

BALL VALVE (TYPICAL)

Y-STRAINER (RECOMMENDED)

STORAGE Number of Units

TANK DRAIN

￿CAUTION

The piping will not support the weight of the water heater circulator pump. Do not attempt to support the weight of the water heater circulator pump with the piping or its accessories. Refer to the pump manufacturer’s installation instructions. Failure to comply could result in severe personal injury, death, or substantial property damage.

NOTICE

Please note that these illustrations are meant to show system piping concept only, the installer is responsible for all equipment and detailing required by local codes.