2 Prepare water heater
Remove water heater from wood pallet
1.After removing the outer shipping carton from the water heater, remove the parts box.
2.Remove the front door to access the lag bolts in front of the unit (FIG.
3.To remove the water heater from the pallet (after removing the front door):
a.Remove the two lag bolts from the wood pallet inside the water heater (FIG.
b.Detach the water heater from the lag bolts in the rear of the unit, see FIG.
NOTICE | Do not drop the water heater or bump the |
jacket on the floor or pallet. Damage to | |
| the water heater can result. |
Figure
Gas conversions
Installation & Operation Manual
Table 2A LP Conversion Table
| LP Conversion Table | |
Model |
| LP Orifice Stamping |
151 |
| 150 |
200 |
| 210 / W150 |
286 |
| 285 |
400 |
| 8.0 |
Models 151 - 286
1. | Remove the top and front access covers from the unit (no | |
| tools required for removal). | |
2. | Remove the three screws securing the gas valve to the | |
| venturi (FIG. | |
3. | Locate the propane orifice disk from the conversion kit bag. | |
| Verify that the stamping on the orifice disk matches the | |
| water heater size (151 – 286) (see Table 2A above). | |
| Place the orifice into the black rubber grommet in the side | |
| of the gas valve and secure in the valve (FIG. | |
4. | Reposition the gas valve against the venturi and replace the | |
| screws (FIG. | |
5. | After installation is complete, attach the propane conversion | |
| label (in the conversion kit bag) next to the water heater | |
| rating plate. Attach the LP caution label (in the conversion | |
| kit bag) to the left side of the unit in the lower left corner. | |
6. | Replace the top and front access covers. | |
| After converting to LP, check combustion | |
WARNING |
WARNING
For a water heater already installed, you must turn off gas supply, turn off power and allow the water heater to cool before proceeding. You must also completely test the water heater after conversion to verify performance as described under Start- up, Section 10 of this manual. Failure to comply could result in severe personal injury, death, or substantial property damage.
For Models 151 - 400 you must install a propane orifice to operate the Armor water heater on propane gas. Verify when installing that the orifice size marking matches water heater size (Models 151 – 400, Table 2A).
The 501 - 801 Models do not require an orifice installation for propane operation, but they will require a valve adjustment.
per the |
of this manual. Failure to check and verify combustion could result in severe personal injury, death, or substantial property damage.
Figure
13