Lochinvar 151 Install vent and combustion air piping, Requirements for installation in Canada

Models: 151

1 76
Download 76 pages 1.76 Kb
Page 18
Image 18
Install vent and combustion air piping

Installation & Operation Manual

3 General venting

Install vent and combustion air piping

The Armor water heater must be vented ￿ DANGER and supplied with combustion and

ventilation air as described in this section. Ensure the vent and air piping and the combustion air supply comply with these instructions regarding vent system, air system, and combustion air quality. See also Section 1 of this manual.

Inspect finished vent and air piping thoroughly to ensure all are airtight and comply with the instructions provided and with all requirements of applicable codes.

Failure to provide a properly installed vent and air system will cause severe personal injury or death.

PVC/CPVC Vent piping materials

￿WARNING Insulation should not be used on PVC or CPVC venting materials. The use of

insulation will cause increased vent wall temperatures, which could result in vent pipe failure.

Requirements for installation in Canada

1.

Installations must be made with a vent pipe system

 

certified to ULC-S636.

 

IPEX is an approved vent manufacturer in Canada

 

supplying vent material listed to ULC-S636.

2.

The first three (3)

feet of plastic vent pipe from the

 

appliance flue outlet must be readily accessible for visual

 

inspection.

 

3.

The components of the certified vent system must not be

 

interchanged with

other vent systems or unlisted

￿WARNING

NOTICE

Use only the materials listed in Table 3A (page 19) for vent pipe, and fittings. Failure to comply could result in severe personal injury, death, or substantial property damage.

Installation must comply with local requirements and with the National Fuel Gas Code, ANSI Z223.1 for U.S. installations or CSA B149.1 for Canadian installations.

pipe/fittings. For concentric vent installations, the inner

vent tube must be replaced with field supplied certified

vent material to comply with this requirement.

4. The 3" Concentric Vent Kit available from Lochinvar (see

Section 4 – Sidewall Termination – Optional Concentric

Vent) and the 3" Concentric Vent Kit available from IPEX

are both approved for use on the Armor water heater.

Both kits are listed to the ULC-S636 standard for use in

Canada.

Improper installation of PVC or CPVC

￿WARNING

NOTICE

For closet and alcove installations, CPVC or stainless steel material MUST BE used in a closet/alcove structure. Failure to follow this warning could result in fire, personal injury, or death.

All PVC vent pipes must be glued, properly supported, and the exhaust must be pitched a minimum of a 1/4 inch per foot back to the water heater (to allow drainage of condensate).

￿ CAUTION systems may result in injury or death.

Installing vent or air piping

NOTICE

Use only cleaners, primers, and solvents that

are approved for the materials which are

 

joined together.

1. Work from the water heater to vent or air termination. Do

not exceed the lengths given in this manual for the air or

vent piping.

￿WARNING

PVC/CPVC Vent piping materials 18 Requirements for installation in Canada

This appliance requires a special venting system. The vent connection to the appliance must be made with the starter CPVC pipe section provided with the appliance if PVC/CPVC vent is to be used. For stainless steel venting use an adapter from Table 3B (page 21) that corresponds with the intended vent manufacturer to be used and discard the CPVC starter piece. The field provided vent fittings must be cemented to the CPVC pipe section using an “All Purpose Cement” suitable for PVC and CPVC pipe. Use only the vent materials, primer, and cement specified in this manual to make the vent connections. Failure to follow this warning could result in fire, personal injury, or death.

2.

Cut pipe to the required lengths and deburr the inside and

 

outside of the pipe ends.

3.

Chamfer outside of each pipe end to ensure even cement

 

distribution when joining.

4.

Clean all pipe ends and fittings using a clean dry rag.

 

(Moisture will retard curing and dirt or grease will prevent

 

adhesion.)

5.

Dry fit vent or air piping to ensure proper fit up before

 

assembling any joint. The pipe should go a third to

 

two-thirds into the fitting to ensure proper sealing after

 

cement is applied.

Page 18
Image 18
Lochinvar 151 Install vent and combustion air piping, Requirements for installation in Canada, General venting, Notice