Lochinvar 151 operation manual Multiple vent/air terminations, Termination and fittings

Models: 151

1 76
Download 76 pages 1.76 Kb
Page 27
Image 27
Multiple vent/air terminations

Installation & Operation Manual

4 Sidewall direct venting (continued)

Prepare wall penetrations (Alternate - Field Supplied Option)

1.Air pipe penetration:

a.Cut a hole for the air pipe. Size the air pipe hole as close as desired to the air pipe outside diameter.

2.Vent pipe penetration:

a.Cut a hole for the vent pipe. For either combustible or noncombustible construction, size the vent pipe hole with at least a 1/2 inch clearance around the vent pipe outer diameter:

4½ inch hole for 3 inch vent pipe

5½ inch hole for 4 inch vent pipe

7½ inch hole (191 mm) hole for 6 inch (152 mm) vent pipe

b.Insert a galvanized metal thimble in the vent pipe hole as shown in FIG. 4-5B.

3.Use a sidewall termination plate as a template for correct location of hole centers.

4.Follow all local codes for isolation of vent pipe when passing through floors or walls.

5.Seal exterior openings thoroughly with exterior caulk.

Figure 4-5BA Typical Sidewall Termination Assembly - Models 151 - 801 PVC/CPVC or Stainless Steel

6.Stainless steel terminations are designed to penetrate walls with a thickness up to 9.25 inches of standard construction.

Multiple vent/air terminations

1. When terminating multiple Armor water heaters terminate each vent/air connection as described in this manual (FIG. 4-6A).

￿WARNING All vent pipes and air inlets must terminate at the same height to avoid possibility of

severe personal injury, death, or substantial property damage.

2.Place wall penetrations to obtain minimum clearance of 12 inches between edge of air inlet and adjacent vent outlet, as shown in FIG. 4-6A for U.S. installations. For Canadian installations, provide clearances required by CSA B149.1 Installation Code.

3.The air inlet of a Armor water heater is part of a direct vent connection. It is not classified as a forced air intake with regard to spacing from adjacent water heater vents.

Figure 4-6AMultiple Vent Terminations (must also comply with Figure 4-1A)

12" MIN. BETWEEN EDGE OF AIR Termination and fittings INLET AND ADJACENT VENT OUTLET

VENT

SIDEWALL

TERMINATION PLATE

VENT

PIPING

BIRD SCREEN

ELBOW Manual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual background BIRD SCREEN

GALVANIZED

THIMBLE (WHEN REQUIRED BY LOCAL CODES)

ELBOW

AIR PIPING

AIR

VENT / AIR

Termination and fittings

TERMINATION

1.Prepare the vent termination elbow and the air termination elbow (FIG. 4-5B) by inserting bird screens. Bird screens can be obtained locally.

2.When completed, the air termination coupling must be oriented at least 12 inches (305 mm) below the vent termination and at least 12 inches (305 mm) above grade or snow line as shown in FIG. 4-1A, page 24.

3.Maintain the required dimensions of the finished termination piping as shown in FIG. 4-1A, page 24.

4.Do not extend exposed vent pipe outside of building more than shown in this document. Condensate could freeze and block vent pipe.

5.PVC/CPVC terminations are designed to accommodate any wall thickness of standard constructions per the directions found in this manual.

Figure 4-6BAlternate Multiple Vent Terminations w/Field Supplied Fittings (must also comply with Figure 4-1B)

Manual background 27 Manual background

Page 27
Image 27
Lochinvar 151 operation manual Multiple vent/air terminations, Termination and fittings, Sidewall direct venting continued