Image 43
Figure 6-8Double Heater - Double Tank

Installation & Operation Manual

6 System piping (continued)

Figure 6-8Double Heater - Double Tank

COLD WATER

SUPPLY

EXPANSION

TANK

FLOW CHECK

VALVE (TYPICAL)

BUILDING Manual background

RETURN

HOT WATER

SUPPLY

THERMOMETER

MIXING VALVE

UNION Manual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual background (TYPICAL) Manual backgroundManual background

TEMPERATURE & PRESSURE RELIEF VALVE (TYPICAL)

STORAGE TANK (TYPICAL)

DRAIN (TYPICAL)

 

 

 

Number of Units

 

 

Model

2

3

4

5

6

7

8

 

 

Required Pipe Sizes in NPT

 

151

1 1/2"

2"

2"

2"

2 1/2"

3"

3"

200

1 1/2"

2"

2 1/2"

2 1/2"

3"

3"

4"

286

2"

2 1/2"

2 1/2"

3"

3"

4"

4"

400

2 1/2"

3"

3 1/2"

4"

4"

5"

5"

501

3"

3 1/2"

4"

5"

5"

5"

6"

601

3"

3 1/2"

4"

5"

5"

5"

6"

701

3"

4"

5"

5"

6"

6"

6"

801

3"

4"

5"

6"

6"

6"

6"

WATER

HEATER (TYPICAL)

FLOW SWITCH (TYPICAL)

WATER HEATER CIRCULATOR (TYPICAL)

Manual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual background BALL VALVE (TYPICAL)

Manual background Y-STRAINER (RECOMMENDED)

￿CAUTION

The piping will not support the weight of the water heater circulator pump. Do not attempt to support the weight of the water heater circulator pump with the piping or its accessories. Refer to the pump manufacturer’s installation instructions. Failure to comply could result in severe personal injury, death, or substantial property damage.

NOTICE

Please note that these illustrations are meant to show system piping concept only, the installer is responsible for all equipment and detailing required by local codes.

Manual background 43 Manual background

Page 43
Image 43
Lochinvar 151 8 Double Heater - Double Tank, System piping continued, Number of Units, Model, Required Pipe Sizes in NPT