8 Field wiring
Installation & Operation Manual
WARNING
NOTICE
CAUTION
ELECTRICAL SHOCK HAZARD – For your safety, turn off electrical power supply before making any electrical connections to avoid possible electric shock hazard. Failure to do so can cause severe personal injury or death.
Wiring must be N.E.C. Class 1.
If original wiring as supplied with the water heater must be replaced, use only type 105°C wire or equivalent.
The water heater must be electrically grounded as required by National Electrical Code ANSI/NFPA 70 – latest edition.
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation.
Installation must comply with:
1.National Electrical Code and any other national, state, provincial, or local codes, or regulations.
2.In Canada, CSA C22.1 Canadian Electrical Code Part 1, and any local codes.
Line voltage connections
1. | Connect 120 VAC power wiring to the line voltage |
| terminal strip in the junction box, as shown in FIG. |
2. | Provide and install a fused disconnect or service switch |
| (15 amp recommended) as required by the code (see |
| FIG. |
3. | The DHW (water heater) pump is shipped loose on all |
| Armor models. Wire the water heater pump as shown in |
| FIG. |
4. | The Armor water heater is capable of controlling a |
| building recirculation pump (field supplied). Wire the |
Figure 8-1 Line Voltage Field Wiring Connections
DOMESTIC | SERVICE |
| 120V SUPPLY | |||
HOT WATER |
|
|
|
| ||
| SWITCH |
| LINE | GROUND | NEUTRAL | |
PUMP |
|
| ||||
L2/N |
|
| BK |
|
| |
W | G | L1 | G | W | ||
G |
|
|
|
|
|
|
BK |
|
|
|
|
|
|
RECIRCULATION |
|
|
|
|
|
|
PUMP | L4/N | G L3 |
|
|
|
|
W |
|
|
|
| ||
|
|
|
|
|
| |
G |
|
|
|
|
|
|
BK |
|
|
|
|
|
|
building recirculation pump as shown in FIG. |
5. Dry contacts are sized for 1 hp/120V, 2 hp/240V or |
15A/120V, 25A/240V. |
Low voltage connections
1.Route all low voltage wires through the knockouts in the rear of the water heater, as shown in FIG.
2.Connect low voltage wiring to low voltage connection board as shown in FIG.
Figure 8-2 Routing Field Wiring (Models 151 - 286)
LOW VOLTAGE
CONNECTION BOARD
LOW VOLTAGE
WIRING KNOCKOUTS
LINE VOLTAGE WIRING KNOCKOUTS
48