4 Sidewall direct venting
Vent/air termination – sidewall
WARNING Follow instructions below when determining vent location to avoid possibility of severe
personal injury, death, or substantial property damage.
WARNING A gas vent extending through an exterior wall shall not terminate adjacent to a wall
or below building extensions such as eaves, parapets, balconies, or decks. Failure to comply could result in severe personal injury, death, or substantial property damage.
Installation & Operation Manual
Figure 4-1A Sidewall Termination of Air and Vent
TO BOILER
INTAKE AIR
CONNECTION
FROM BOILER
VENT PIPE
CONNECTION
12"
POSSIBLE ORIENTATIONS | MIN |
TO
OVER-
HANG
VENT / AIR
TERMINATION
12"
MIN
WARNING
NOTICE
Do not connect any other appliance to the vent pipe or multiple water heaters to a common vent pipe. Failure to comply could result in severe personal injury, death, or substantial property damage.
Installation must comply with local requirements and with the National Fuel Gas Code, ANSI Z223.1 for U.S. installations or CSA B149.1 for Canadian installations.
|
| GRADE OR |
|
| SNOW LINE |
Table 4A Sidewall Vent Kits |
| |
Model | Kit Number | Vent Size |
151 - 200 | KIT30045 | 3 inch vent |
286 - 601 | KIT30046 | 4 inch vent |
Determine location
Locate the vent/air terminations using the following guidelines:
1.The total length of piping for vent or air must not exceed the limits given in the General Venting Section on page 22 of this manual.
2.You must consider the surroundings when terminating the vent and air:
a.Position the vent termination where vapors will not damage nearby shrubs, plants or air conditioning equipment or be objectionable.
b.The flue products will form a noticeable plume as they condense in cold air. Avoid areas where the plume could obstruct window views.
c.Prevailing winds could cause freezing of condensate and water/ice buildup where flue products impinge on building surfaces or plants.
d.Avoid possibility of accidental contact of flue products with people or pets.
e.Do not locate the terminations where wind eddies could affect performance or cause recirculation, such as inside building corners, near adjacent buildings or surfaces, window wells, stairwells, alcoves, courtyards, or other recessed areas.
WARNING Sidewall vent and air inlet terminations must terminate in the same pressure zone.
f.Do not terminate above any door or window. Condensate can freeze, causing ice formations.
g.Locate or guard vent to prevent condensate damage to exterior finishes.
24
701 - 801 | KIT30048 | 6 inch vent |
3.The air piping must terminate in a
4.The vent piping must terminate in an elbow pointed outward or away from the air inlet, as shown in FIG.
WARNING Do not exceed the maximum lengths of the outside vent piping shown in FIG.
Excessive length exposed to the outside could cause freezing of condensate in the vent pipe, resulting in potential water heater shutdown.
Figure
TO BOILER
INTAKE AIRBIRD SCREEN
CONNECTION
FROM BOILER | 12” MIN | |
VENT PIPE | ||
15” MAX | ||
CONNECTION | ||
|
TERMINATION
PLATE
12”
MIN
BIRD
SCREEN
GRADE OR
SNOW LINE