3General venting
Installation & Operation Manual
WARNING
When utilizing the single pipe method, provisions for combustion and ventilation air must be in accordance with Air for Combustion and Ventilation, of the latest edition of the National Fuel Gas Code, ANSI Z223.1, in Canada, the latest edition
WARNING If the boiler combustion air inlet is located in a laundry room or pool
facility, for example, these areas will
always contain hazardous contaminants.
of CGA Standard B149 Installation Code for Gas Burning Appliances and Equipment, or applicable provisions of the local building codes.
WARNING
To prevent the potential of severe personal injury or death, check for areas and products listed in Table 1A, page 11 before installing the boiler or air inlet piping.
Table 3F Optional Room Air Kit
Model | Description | Kit Number | |
|
|
| |
399 - 800 | Filter Box Assembly | KIT30022 | |
|
| ||
90° Elbow with Screen | KIT30053 | ||
| |||
|
|
|
Air contamination
Pool and laundry products and common household and hobby products often contain fluorine or chlorine compounds. When these chemicals pass through the boiler, they can form strong acids. The acid can eat through the boiler wall, causing serious damage and presenting a possible threat of flue gas spillage or boiler water leakage into the building.
Please read the information given in Table 1A, page 11, listing contaminants and areas likely to contain them. If contaminating chemicals will be present near the location of the boiler combustion air inlet, have your installer pipe the boiler combustion air and vent to another location, per this manual.
If contaminants are found, you MUST:
•Remove products permanently.
•Relocate air inlet and vent terminations to other areas.
22