11 Operating information (continued)

Status Display Screens (cont’d)

By using the Previous/Next (￿, ￿) arrow keys on the SMART SYSTEM display panel, you can navigate through the eight (8) display screens. Each screen will contain two (2) viewable items. The following is a description of the individual items and what they can display:

Screen

Display shows:

Description

 

DHW PUMP: OFF

The control has not received a DHW call for heat and has not

 

powered the DHW pump.

 

 

 

 

 

 

ON

The control has received a DHW call for heat and has powered the

 

DHW pump.

#7

 

 

 

Delay

The DHW call for heat has been satisfied and the DHW pump is

 

 

running for a fixed time to remove any residual heat.

 

 

 

 

 

 

0-10V IN: **.Vdc

The control will display a 0-10Vdc signal received from a Building

 

Management System (BMS) connected to the unit.

 

 

 

 

 

Press the Next ￿ arrow key on the SMART SYSTEM display to access Screen #8.

#8

SYS PUMP: OFF

The control has not received a call for heat from a remote thermostat

and has not powered the system pump.

 

 

 

ON

The control has received a call for heat from a remote thermostat and

has powered the system pump.

 

 

 

Delay

The system call for heat has been satisfied and the system pump is

running for a fixed time to remove any residual heat.

 

 

 

 

The control has either not received a call for heat from a remote

 

thermostat, a remote thermostat is not connected to the unit and the

BLR PUMP: OFF

water temperature has not dropped below the temperature set point

 

of the control to initiate a call for heat, or the control has received a

 

DHW call for heat from a DHW thermostat.

 

 

 

The control has received a call for heat from a remote thermostat or a

ON

remote thermostat is not connected and the water temperature has

dropped below the temperature set point of the control to initiate a

 

 

call for heat.

 

 

Delay

The call for heat has been satisfied and the boiler pump is running for

a fixed time to remove any residual heat.

 

 

 

Press the Next ￿ arrow key on the SMART SYSTEM display to access Screen #9.