Lochinvar 399 operation manual 4Sidewall direct venting continued, Installation & Operation Manual

Models: 399

1 76
Download 76 pages 58.86 Kb
Page 27
Image 27
Description and usage

Installation & Operation Manual

4Sidewall direct venting (continued)

Sidewall termination – optional concentric vent: Models 399 - 600 Only

Description and usage

Lochinvar offers an optional concentric combustion air and

3. You must consider the surroundings when terminating the

vent pipe termination kit (#CVK3007 for 4" (102 mm)

vent and air:

 

diameter - Models 399 - 600). Both combustion air and vent

a.

Position the vent termination where vapors will not

pipes must attach to the termination kit. The termination kit

 

damage nearby shrubs, plants or air conditioning

must terminate outside the structure and must be installed as

 

equipment or be objectionable.

shown below in FIG. 4-7.

b.

The flue products will form a noticeable plume as

Field supplied pipe and fittings are required to complete the

 

they condense in cold air.

Avoid areas where the

 

plume could obstruct window views.

installation.

 

c.

Prevailing winds could cause freezing of condensate

 

The required combustion vent pipe materials are listed in

 

and water/ice buildup where flue products impinge

 

on building surfaces or plants.

Table 3A, on page 18 of this manual.

 

d.

Avoid possibility of accidental contact of flue

 

 

 

products with people or pets.

 

Figure 4-7Concentric Sidewall Termination - Models

 

 

f.

Do not terminate above

any door or window.

399 - 600

 

Condensate can freeze, causing ice formations.

 

 

OVERHANG

g.

Locate or guard vent to prevent condensate damage

OR ROOF

 

to exterior finishes.

 

 

 

 

12" (305 MM)

MIN

12" (305 MM)

MIN

GRADE / SNOW LINE

Sidewall termination installation

1.Determine the best location for the termination kit (see FIG. 4-7).

2.The total length of piping for vent or air must not exceed the limits given in the General Venting section on page 21 of this manual.

Figure 4-8Kit Contents_CVK3007 - Models 399 - 600

RAIN CAP

6" (152 MM) TO 4" (102 MM) REDUCER

6" (152 MM) DIA.

399 - 600 6" (152 MM) DIA.

4" (102 MM) DIA.

"Y" CONCENTRIC FITTING

6" (152 MM) DIA.

"FLEXIBLE" PIPE COUPLING

4.Cut one (1) hole (7 inch (178 mm) diameter for #CVK3007 installations into the structure to install the termination kit.

5.Partially assemble the concentric vent termination kit. Clean and cement using the procedures found in these instructions.

a.Cement the Y concentric fitting to the larger kit pipe (FIG. 4-8).

b.Cement the rain cap to the smaller diameter kit pipe (FIG. 4-8).

Sidewall termination installation 27 Figure 4-8Kit Contents_CVK3007 - Models 399 - 600

Page 27
Image 27
Lochinvar 399 operation manual 4Sidewall direct venting continued, Installation & Operation Manual, Description and usage