Installation & Operation Manual
11 Operating information (continued)
Status Display Screens
By using the Previous/Next (, ) arrow keys on the SMART SYSTEM display panel, you can navigate through the eight (8) display screens. Each screen will contain two (2) viewable items. The following is a description of the individual items and what they can display:
Screen |
| Display shows: | Description |
|
| BLR: OFF | The unit has been turned OFF by the Enter/Reset button on the |
|
| SMART SYSTEM display panel. | |
|
|
| |
|
|
|
|
|
| Standby | The unit has not received a call for heat from a remote thermostat nor |
|
| has it received a call for heat from a DHW thermostat. | |
|
|
| |
|
|
|
|
|
| Set Point Met | The unit has met the water temperature set point, but is still receiving |
|
| a call for heat from either a remote thermostat or a DHW thermostat. | |
|
|
| |
|
|
|
|
|
|
| The unit has initiated a 10 second purge period on a call for heat. |
|
| Prepurge | Note: On the 800 model the unit will initiate a 20 second purge |
|
|
| period on a call for heat. |
|
|
|
|
|
| Ignition | The unit has begun a 5 second spark period to ignite the main burner. |
|
|
|
|
#1 |
| SH***% Rate | The unit has fired and is running at the displayed percentage. |
|
|
| |
|
| The call for heat has been satisfied and the unit runs the fan for an | |
|
|
| |
|
| Postpurge | additional 10 seconds to clear the combustion chamber and vent |
|
|
| system of residual flue products. |
|
|
|
|
|
| Service | The unit has been placed in a temporary mode that will allow the unit |
|
| to fire at 100% of rate for the purpose of combustion analysis. | |
|
|
| |
|
|
|
|
|
|
| When the outlet sensor has been selected as the control sensor |
|
| OUT: ***.*F(***) | (default), the control will display the outlet temperature as well as the |
|
|
| set point in parenthesis. |
|
|
|
|
|
| ***.*F | If the outlet sensor has not been selected as the control sensor, only |
|
| the outlet temperature will be displayed. | |
|
|
| |
|
|
|
|
|
| Open | The control does not detect the outlet sensor. |
|
|
|
|
|
| Shorted | The outlet sensor wires or the sensor itself has become shorted. |
|
|
|
|
| Press | the Next arrow key on the | SMART SYSTEM display to access Screen #2. |
|
| IN: ***.*F | If the inlet sensor has not been selected as the control sensor, only the |
|
| inlet temperature will be displayed. | |
|
|
| |
|
|
|
|
|
|
| When the inlet sensor has been selected as the control sensor, the |
|
| ***.*F (***) | control will display the inlet temperature as well as the set point in |
#2 |
|
| parenthesis. |
|
|
| |
|
| Open | The control does not detect the inlet sensor. |
|
|
|
|
|
| Shorted | The inlet sensor wires or the sensor itself has become shorted. |
|
|
|
|
|
| RISE: ***.*F | The difference between the inlet temperature and the outlet |
|
| temperature. | |
|
|
| |
|
|
|
|
| Press | the Next arrow key on the | SMART SYSTEM display to access Screen #3. |
|
|
|
|
63