Figure 5-6Concentric Vent Roof Installation

Installation & Operation Manual

5Vertical direct venting (continued)

Vertical termination – optional concentric vent: Models 399 - 600 Only

￿WARNING

Do not operate the appliance with the rain cap removed or recirculation of combustion products may occur. Water may also collect inside the larger combustion air pipe and flow to the burner enclosure. Failure to follow this warning could result in product damage or improper operation, personal injury, or death.

CAUTION

DO NOT use field-supplied couplings to

extend pipes. Airflow restriction will

 

 

occur.

6.

Install the rain cap and the small diameter pipe assembly

 

into the roof penetration assembly. Ensure the small

 

diameter pipe is fastened tightly into the rubber adapter

 

for #CVK3007 installations.

7.

Cement the appliance combustion air and vent pipes to

4.Install the Y concentric fitting pipe assembly up through the structure’s hole and field supplied roof boot/flashing.

NOTICE

Do not allow insulation or other materials

to accumulate inside the pipe assembly

 

 

when installing through the hole.

5.Secure the assembly to the roof structure as shown below in FIG. 5-6 using field supplied metal strapping or equivalent support material.

Figure 5-6Concentric Vent Roof Installation

the concentric vent termination assembly. See FIG. 5-6

for proper pipe attachment.

8. Operate the appliance through one (1) heat cycle to

ensure combustion air and vent pipes are properly

connected to the concentric vent termination

connections.

Multiventing vertical terminations

When two (2) or more direct vent appliances are vented near each other, each appliance must be individually vented (see FIG. 5-7). NEVER common vent or breach vent this

COMBUSTION

AIR

ROOF BOOT / FLASHING (FIELD SUPPLIED)

VENT

12" (305 MM) (18" (457 MM) FOR CANADA)

MINIMUM CLEARANCE ABOVE HIGHEST ANTICIPATED SNOW LEVEL. MAXIMUM OF 24” (610 MM) ABOVE ROOF.

Multiventing vertical terminationsManual backgroundManual background SUPPORT (FIELD SUPPLIED)

ELBOW

(FIELD SUPPLIED)

appliance. When two (2) or more direct vent appliances are vented near each other, two (2) vent terminations may be installed as shown in FIG. 5-7. The next two (2) terminations must be at least 36 inches (914 mm) away from the first two

(2)terminations. It is important that vent terminations be made as shown to avoid recirculation of flue gases. Dimension A in FIG. 5-7 represents the distance between pipes or rain shields, as touching or a 2 inch (51 mm) maximum separation.

Figure 5-7Concentric Vent and Combustion Air Vertical Termination (Dimension A as Touching or 2 inches (51 mm) Maximum Separation)

Manual backgroundManual background"A"

VENT

COMBUSTION

 

AIR

NOTICE

Ensure termination height is above the

roof surface or anticipated snow level

 

 

 

(12 inches (305 mm) in U.S.A. or 18

 

inches (457 mm) in Canada) as shown in

 

FIG. 5-4, page 32.

 

If assembly is too short to meet height

NOTICE

requirement, the two (2) pipes supplied in

 

 

the kit may be replaced by using the same

36" (914 MM)

MIN.

VENT (TYP)

COMBUSTION AIR (TYPICAL)

diameter, field supplied standard schedule

40 PVC for CVK3007. Do not extend

dimension D* more than 60 inches

(1524 mm) (see FIG. 4-9, page 28).

12" (305 MM) (18" (457 MM)

 

 

FOR CANADA) MINIMUM

 

DIMENSTION "A" IS TOUCHING

 

 

 

CLEARANCE ABOVE

 

OR 2" (51 MM) MAXIMUM

 

 

HIGHEST ANTICIPATED

 

SEPARATION

SNOW LEVEL. MAXIMUM OF

 

 

24" (610 MM) ABOVE ROOF.

 

 