Lochinvar 399 Please read before proceeding, When servicing boiler, Boiler operation

Models: 399

1 76
Download 76 pages 58.86 Kb
Page 3
Image 3
Installation & Operation Manual

Installation & Operation Manual

Please read before proceeding

￿WARNING

NOTICE

Installer – Read all instructions, including this manual and the Knight XL Service Manual, before installing. Perform steps in the order given.

User – This manual is for use only by a qualified heating installer/service

technician. Refer to the User’s Information Manual for your reference.

Have this boiler serviced/inspected by a qualified service technician, at least annually.

Failure to comply with the above could result in severe personal injury, death or substantial property damage.

When calling or writing about the boiler – Please have the boiler model and serial number from the boiler rating plate.

Consider piping and installation when determining boiler location.

When servicing boiler –

To avoid electric shock, disconnect electrical supply before performing maintenance.

To avoid severe burns, allow boiler to cool before performing maintenance.

Boiler operation –

Do not block flow of combustion or ventilation air to the boiler.

Should overheating occur or gas supply fail to shut off, do not turn off or disconnect electrical supply to circulator. Instead, shut off the gas supply at a location external to the appliance.

Do not use this boiler if any part has been under water. The possible damage to a flooded appliance can be extensive and present numerous safety hazards. Any appliance that has been under water must be replaced.

￿WARNING

￿WARNING

Any claims for damage or shortage in shipment must be filed immediately against the transportation company by the consignee.

Factory warranty (shipped with unit) does not apply to units improperly installed or improperly operated.

Failure to adhere to the guidelines on this page can result in severe personal injury, death, or substantial property damage.

If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life.

This appliance MUST NOT be installed in any location where gasoline or flammable vapors are likely to be present.

Boiler water –

• Thoroughly flush the system (without boiler

connected) to remove sediment. The high-efficiency

heat exchanger can be damaged by build-up or

corrosion due to sediment.

• Do not use petroleum-based cleaning or sealing

compounds in the boiler system. Gaskets and seals in

the system may be damaged. This can result in

substantial property damage.

• Do not use “homemade cures” or “boiler patent

medicines”. Serious damage to the boiler, personnel,

and/or property may result.

• Continual fresh make-up water will reduce boiler life.

Mineral buildup in the heat exchanger reduces heat

transfer, overheats the stainless steel heat exchanger,

and causes failure. Addition of oxygen carried in by

makeup water can cause internal corrosion in system

components. Leaks in boiler or piping must be repaired

WHAT TO DO IF YOU SMELL GAS

Do not try to light any appliance.

Do not touch any electric switch; do not use any phone in your building.

Immediately call your gas supplier from a near by phone. Follow the gas supplier’s instructions.

If you cannot reach your gas supplier, call the fire department.

Installation and service must be performed by a qualified installer, service agency, or the gas supplier.

at once to prevent makeup water.

Freeze protection fluids –

NEVER use automotive antifreeze. Use only inhibited propylene glycol solutions, which are specifically formulated for hydronic systems. Ethylene glycol is toxic and can attack gaskets and seals used in hydronic systems.

3

Page 3
Image 3
Lochinvar 399 operation manual Please read before proceeding, When servicing boiler, Boiler operation, Boiler water