Lochinvar 399 operation manual Sidewall direct venting, Vent/air termination – sidewall

Models: 399

1 76
Download 76 pages 58.86 Kb
Page 24
Image 24
Figure 4-1DAlternate PVC/CPVC/SS Vent Termination

Installation & Operation Manual

4 Sidewall direct venting

Vent/air termination – sidewall

Figure 4-1CAlternate Stainless Steel Vent Termination

-Typical Stainless Steel Sidewall Termination of Air and Vent Models 399 - 600 w/Field Supplied Fittings, Utilizing FasNSeal’s Hood Intake. Available Through FasNSeal Only

Figure 4-2BAlternate Stainless Steel Sidewall Termination Models 700 - 800 w/Field Supplied Fittings

BIRD SCREEN

TO BOILER

INTAKE AIR

CONNECTION

12" (305 MM) MIN 15" (381 MM) MAX

TO BOILER INTAKE AIR CONNECTION

FROM BOILER VENT PIPE CONNECTION

12" (305 MM) MIN 15" (381 MM) MAX

FROM BOILER

VENT PIPE

CONNECTION

12" (305 MM) MIN

Figure 4-1DAlternate PVC/CPVC/SS Vent Termination

-Typical Stainless Steel Sidewall Termination of Air and Vent Models 399 - 600 w/Field Supplied Fittings, Utilizing 90° Elbow Intake

TO BOILER

INTAKE AIR

CONNECTION

FROM BOILER

 

VENT PIPE

 

CONNECTION

12" MIN

 

15" MAX

12" MIN

BIRD SCREEN

Figure 4-2AAlternate PVC/CPVC Sidewall Termination Models 399 - 800 w/Field Supplied Fittings

Figure 4-3AClearance to Gravity Air Inlets 12" (305 MM) MIN

NOTICE PVC/CPVC or ABS is acceptable air inlet pipe material.

5.Maintain clearances as shown in FIG.’s 4-1A thru 4-4B, pages 23 thru 25. Also maintain the following:

a.Vent must terminate:

At least 6 feet (1.8 m) from adjacent walls.

No closer than 12 inches (305 mm) below roof overhang.

At least 7 feet (2.1 m) above any public walkway.

At least 3 feet (.9 m) above any forced air intake within 10 feet (3 m).

No closer than 12 inches (305 mm) below or horizontally from any door or window or any other gravity air inlet.

b.Air inlet must terminate at least 12 inches (305 mm) above grade or snow line; at least 12 inches (305 mm) below the vent termination (FIG. 4-1B); and the vent pipe must not extend more than 24 inches (610 mm) vertically outside the building.

c.Do not terminate closer than 4 feet (1.2 m) horizontally from any electric meter, gas meter, regulator, relief valve, or other equipment. Never terminate above or below any of these within 4 feet (1.2 m) horizontally.

6.Locate terminations so they are not likely to be damaged by foreign objects, such as stones or balls, or subject to buildup of leaves or sediment.

TO BOILER

INTAKE AIR

CONNECTION

FROM BOILER

VENT PIPE

CONNECTION

Manual background 24 Manual background

BIRD SCREEN

12" (305 MM) MIN 15" (381 MM) MAX

BIRD SCREEN

12" (305 MM) MIN

Figure 4-3AClearance to Gravity Air Inlets

12"

MIN.

VENT / AIR

TERMINATION

12" Manual backgroundMIN.

12" Manual backgroundMIN.

Page 24
Image 24
Lochinvar 399 operation manual Sidewall direct venting, Vent/air termination – sidewall, Installation & Operation Manual