Installation & Operation Manual

7Gas connections (continued)

Table 7A Natural Gas Pipe Size Chart

Nominal

 

 

 

 

Natural Gas Pipe Capacity Chart

 

 

 

 

Maximum

Iron Pipe

 

 

 

 

 

 

 

 

Capacity of Pipe

 

 

 

 

Length of Pipe in Straight Feet

 

 

 

 

Size

 

 

 

 

 

 

 

 

in Thousands of

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Btu/hr per hour

(inches)

10

20

30

40

50

60

70

80

90

100

125

150

175

200

for gas pressures

 

1/2

175

120

97

82

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

of 14 Inches

Water Column

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3/4

369

256

205

174

155

141

128

121

113

106

95

86

79

74

(0.5 PSIG) or less

1

697

477

384

328

292

267

246

236

210

200

179

164

149

138

and a pressure

1-1/4

1400

974

789

677

595

543

502

472

441

410

369

333

308

287

drop of 0.5 Inch

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Water Column

1-1/2

2150

1500

1210

1020

923

830

769

707

666

636

564

513

472

441

(Based on NAT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

4100

2820

2260

1950

1720

1560

1440

1330

1250

1180

1100

974

871

820

GAS, 1025 Btu/hr

2-1/2

6460

4460

3610

3100

2720

2460

2310

2100

2000

1900

1700

1540

1400

1300

per Cubic Foot of

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Gas and 0.60

3

11200

7900

6400

5400

4870

4410

4000

3800

3540

3330

3000

2720

2500

2340

Specific Gravity)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

23500

16100

13100

11100

10000

9000

8300

7690

7380

6870

6150

5640

5130

4720

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check inlet gas supply

NOTICE

CSA or UL listed flexible gas connections are acceptable, but you must exercise caution to ensure that the line has adequate capacity to allow your boiler to fire at full rate. Consult with local codes for proper installation or service procedures.

4.

Slowly turn on the gas supply at the field installed

 

manual gas valve.

5.

Turn the power switch to the “ON” position.

6.

Adjust the temperature set point on the control panel of

 

the SMART SYSTEM control module to call for heat.

7.

Observe the gas supply pressure as the burner fires at

￿WARNING DO NOT adjust or attempt to measure gas valve outlet pressure. Attempting to alter

or measure the gas valve outlet pressure could result in damage to the valve, causing potential severe personal injury, death, or substantial property damage.

The gas piping must be sized for the proper flow and length of pipe, to avoid excessive pressure drop. Both the gas meter and the gas regulator must be properly sized for the total gas load.

If you experience a pressure drop greater than 1 inch w.c. (249 Pa), the meter, regulator, or gas line is undersized or in need of service. Perform the steps below when checking inlet gas supply:

1.Turn the main power switch to the “OFF” position.

2.Shut off gas supply at the manual gas valve in the gas piping to the appliance.

3.On Models 399 - 500 loosen the set screw one (1) full turn from inside the pressure tap on top of the gas valve. On Models 600 - 800 remove the 1/8" (3 mm) pipe plug on the inlet flange to the valve and install a suitable 1/8" (3 mm) fitting (field supplied) for the manometer tubing. Place the tubing of the manometer over the tap once the set screw is loosened or the 1/8" (3 mm) fitting is installed (depending on model) as shown in FIG.’s 7-5 thru 7-7 on page 44.

 

100% of rated input. Percent of burner input will be

 

displayed on the control panel.

8.

Ensure inlet pressure is within specified range.

 

Minimum and maximum gas supply pressures are

 

specified in this section of the manual.

9.

If gas supply pressure is within normal range and no

 

adjustments are needed, proceed on to Step 11.

10.

If the gas pressure is out of range, contact the gas utility,

 

gas supplier, qualified installer or service agency to

 

determine the necessary steps to provide proper gas

 

pressure to the control.

11.

Turn the power switch to the “OFF” position.

12.

Shut off the gas supply at the manual gas valve in the gas

 

piping to the appliance.

13.

Remove the manometer from the pressure tap on top of

 

the gas valve. On Models 399 - 500 re-tighten the set

 

screw inside the pressure tap. On Models 600 - 800

 

remove the 1/8" (3 mm) field supplied fitting and

 

reinstall the pipe plug removed in Step 3.

43

Page 43
Image 43
Lochinvar 399 Check inlet gas supply, Nominal Natural Gas Pipe Capacity Chart, Iron Pipe, Length of Pipe in Straight Feet

399 specifications

Lochinvar 999 - 750, CF-CH(E)-i&s-08,399 is a cutting-edge boiler designed for commercial heating applications. With its robust construction and high efficiency, this model stands out in the crowded market of heating solutions.

One of the main features of the Lochinvar 999 - 750 is its exceptional thermal efficiency rating. The unit incorporates advanced condensing technology that allows it to recover heat from flue gases, which helps in achieving efficiency levels of up to 99%. This efficiency not only reduces energy consumption but also lowers operational costs, making it an excellent investment for businesses looking to minimize their carbon footprint.

The boiler is designed to provide a powerful output of 750 kW, ensuring it meets the heating demands of larger buildings or commercial spaces. Its capacity makes it suitable for a range of applications including schools, hospitals, and industrial facilities. Moreover, the unit features a built-in cascading system that enables multiple boilers to be connected, enhancing system reliability and flexibility.

In terms of technology, the Lochinvar 999 - 750 is equipped with a user-friendly touchscreen interface. This innovative control system allows operators to monitor and adjust settings with ease, providing real-time performance data and alerts for maintenance needs. The intelligent controls optimize operation to match the heating load, further enhancing energy efficiency.

Safety is a top priority with this model. It is built with multiple safety features such as automatic shut-off valves, pressure relief valves, and flame monitoring systems, ensuring safe operation under various conditions. The unit also adheres to stringent industry standards and regulations, making it a reliable choice for commercial applications.

Furthermore, the Lochinvar 999 - 750 is designed with serviceability in mind. Its compact footprint and accessible components simplify maintenance, reducing downtime and associated costs. The unit also supports a variety of fuel sources, including natural gas, propane, and biodiesel, providing flexibility to meet different facility requirements.

In summary, the Lochinvar 999 - 750, CF-CH(E)-i&s-08,399 represents a blend of efficiency, reliability, and safety in commercial heating. Its advanced technologies and thoughtful design make it a powerful solution for various heating needs, making it an ideal choice for businesses aiming for excellence in energy management and operational efficiency.