Lochinvar 399 Installation & Operation Manual, Check for gas leaks, Check thermostat circuits

Models: 399

1 76
Download 76 pages 58.86 Kb
Page 51
Image 51
Check for gas leaks

Installation & Operation Manual

10 Start-up(continued)

Check for gas leaks

￿WARNING

Propane boilers only – Your propane supplier mixes an odorant with the

￿WARNING

￿WARNING

Before starting the boiler, and during initial operation, smell near the floor and around the boiler for gas odorant or any unusual odor. Remove the top access panel and smell the interior of the boiler enclosure. Do not proceed with startup if there is any indication of a gas leak. Use an approved leak detection solution. Repair any leaks at once.

DO NOT adjust or attempt to measure gas valve outlet pressure. The gas valve is factory set for the correct outlet pressure. This setting is suitable for natural gas and propane, requiring no field adjustment. Attempting to alter or measure the gas valve outlet pressure could result in damage to the valve, causing potential severe personal injury, death, or substantial property damage.

propane to make its presence detectable. In some instances, the odorant can fade, and the gas may no longer have an odor. Before startup (and periodically thereafter), have the propane supplier verify the correct odorant level in the gas.

Check thermostat circuit(s)

1.

Disconnect the two external wires connected to the room

 

thermostat terminals on the connection board.

2.

Connect a voltmeter across these two incoming wires.

 

Close each thermostat, zone valve, and relay in the

 

external circuit one at a time and check the voltmeter

 

reading across the incoming wires.

3.

There should NEVER be a voltage reading.

4.

If a voltage does occur under any condition, check and

 

correct the external wiring. (This is a common problem

 

when using 3-wire zone valves.)

Figure 10-1Condensate Trap

RETAINING

SCREW

2” PVC CAP WITH

BLOCKED DRAIN SWITCH

PVC TEE ASSEMBLY (FACTORY SUPPLIED)

CONDENSATE FROM

HEAT EXCHANGER Check thermostat circuit(s)TO FLOOR

DRAIN

5. Once the external thermostat circuit wiring is checked

and corrected if necessary, reconnect the external

thermostat circuit wires to the connection board. Allow

the boiler to cycle.

Inspect/fill condensate system

Inspect/check condensate lines and fittings

1.Inspect the condensate drain line, condensate PVC fittings and condensate trap.

Fill condensate trap with water

1.Remove the PVC cap retaining screw from the PVC cap (FIG. 10-1).

2.Remove the 2 inch PVC cap with the switch located at the top of the trap (FIG. 10-1).

3.Fill with fresh water until the water begins to pour out of the drain.

4.Replace the cap. Press the cap onto the trap until the cap makes contact with the drain.

5.Replace the retaining screw.

The condensate trap (FIG. 10-1) must be ￿ WARNING filled with water during all times of boiler

operation to avoid flue gas emission from the condensate drain line. Failure to fill the trap could result in severe personal injury or death.

Figure 10-1Condensate Trap 51 Inspect/fill condensate system

Page 51
Image 51
Lochinvar 399 Installation & Operation Manual, Check for gas leaks, Check thermostat circuits, 1 Condensate Trap