Lochinvar 399 5Vertical direct venting, Vent/air termination – vertical, Determine location

Models: 399

1 76
Download 76 pages 58.86 Kb
Page 30
Image 30
5Vertical direct venting

Installation & Operation Manual

5Vertical direct venting

Vent/air termination – vertical

￿WARNING

￿WARNING

NOTICE

Follow instructions below when determining vent location to avoid possibility of severe personal injury, death or substantial property damage.

Do not connect any other appliance to the vent pipe or multiple boilers to a common vent pipe. Failure to comply could result in severe personal injury, death, or substantial property damage.

Installation must comply with local requirements and with the National Fuel Gas Code, ANSI Z223.1 for U.S. installations or CSA B149.1 for Canadian installations.

￿WARNING Rooftop vent and air inlet terminations must terminate in the same pressure zone,

unless vertical vent sidewall air is set up as shown in the General Venting - Vertical Vent, Sidewall Air Section.

Figure 5-1APVC/CPVC Vertical Termination of Air and Vent

ALTERNATE INTAKE LOCATIONS:

INTAKE PIPES MAY BE LOCATED

ANYWHERE WITHIN 24" (610 MM)

OF VENT PIPE

BIRD SCREEN

(TYPICAL)

VENT

Determine location

Locate the vent/air terminations using the following guidelines:

1. The total length of piping for vent or air must not exceed

the limits given in the General Venting Section on page 21

of this manual.

COUPLING (FIELD SUPPLIED)

VENT OUTLET

12" MINIMUM ABOVE AIR INLET

6" (152 MM) MINIMUM Vent/air termination – vertical ABOVE ROOF /

SNOW LINE

COMBUSTION

AIR

2. The vent must terminate at least 3 feet above the highest

place in which the vent penetrates the roof and at least

2 feet above any part of a building within 10 horizontal

feet.

3. The air piping must terminate in a down-turned 180°

return pipe no further than 2 feet (.6 m) from the center

of the vent pipe. This placement avoids recirculation of

flue products into the combustion air stream.

4. The vent piping must terminate in an up-turned coupling

as shown in FIG. 5-1A. The top of the coupling must be

at least 1 foot above the air intake. When the vent

termination uses a rain cap as illustrated in FIG. 5-1B

maintain at least 36" (914 mm) above the air inlet. The

air inlet pipe and vent pipe can be located in any desired

position on the roof, but must always be no further than

2 feet (.6 m) apart and with the vent termination at least

1 foot above the air intake.

Figure 5-1BStainless Steel Vertical Termination of Air and Vent

ALTERNATE INTAKE LOCATIONS:

INTAKE PIPES MAY BE LOCATED

ANYWHERE WITHIN 24” (610 MM)

OF VENT PIPE

VENT

BIRD SCREEN

(TYPICAL)

6" (152 MM) MINIMUM

ABOVE ROOF /

SNOW LINE

COM,BUSTION

AIR

VENT OUTLET

36” (914 MM) MINIMUM

ABOVE AIR INLET

5.Locate terminations so they are not likely to be damaged by foreign objects, such as stones or balls, or subject to buildup of leaves or sediment.

Manual background 30 Manual background

Page 30
Image 30
Lochinvar 399 operation manual 5Vertical direct venting, Vent/air termination – vertical, Installation & Operation Manual