Installation (For Qualified Installers Only)

1 5

Installation Example: Interior Vertical Installation

Floor Protection

Vertical Cap

24” Minimum

Storm Collar

Roof Flashing

3”

 

Minimum

2”

 

 

Minimum

 

“Tee”

 

7” Minimum

6” Minimum

 

Insulation must maintain 3” clearance.

Vent must

maintain 3”

clearance to

combustibles.

3” Min.

Ceiling Support / Fire Stop Spacer

“L” Vent

.RTV °F 500Silicone

Seal each vent section (including adapters, elbows, etc...) by injecting a liberal amount of 500° F. RTV silicone into the gap between sections.

2” Min.

Floor Protection

Outside air may be drawn from a ventilated crawl space.

Travis Industries

4061016

1 0 0 - 0 1 1 8 4

Page 15
Image 15
Lopi Leyden Pellet Stove Installation Example Interior Vertical Installation, Min Ceiling Support / Fire Stop Spacer Vent