Mobile Home Requirements

Installation (For Qualified Installers Only)

1 1

Mobile Home Requirements

Outside air is required (used for combustion) - see the directions below.

The heater must be bolted to the floor (Some states do not require this; check with your local building department). See the illustration to the right.

The heater must be grounded to the steel chassis of the mobile home (Some states do not require this; check with your local building department).

WARNING: DO NOT INSTALL IN SLEEPING ROOM.

CAUTION: THE STRUCTURAL INTEGRITY OF THE MANUFACTURED HOME FLOOR, WALL, AND CEILING/ROOF MUST BE MAINTAINED.

The leveling bolts in the legs may be used in conjunction with the included clips (sku

210-03924) to secure the stove to the floor.

Outside Air (used for combustion)

Must not be drawn from an enclosed space (garage, unventilated crawl space).

HINT:

Travis Industries strongly suggests outside air for all residential installations, especially for

 

those that are energy efficient, air-tight homes.

Must not be over 15' long (the kit includes a 4’ length – additional 3” diameter duct may be used).

Must be made with 3" diameter or larger metal or aluminum duct with a metal screen attached to the end to keep out rodents (P.V.C. or other combustible materials may not be used). We recommend the Travis Industries Outside Air Kit (part # 99200136).

Must not terminate above or within 1' of the chimney termination.

Must have a rain cap or down-turned elbow to prevent water from entering.

Must be located so that it will not become plugged by snow or other material.

A screen is required to prevent rodents from entering.

3” Diameter Air Duct

Air may be drawn from a ventilated crawl space.

Outside air entrance must be placed so it does not become blocked by snow.

Botttom of Stove

Use a hose clamp to secure the aluminum air duct to the air inlet flange on the stove.

Air Duct (3” Dia.)

Travis Industries

4061016