Installation (For Qualified Installers Only)

9

Venting the Pellet Stove

PELLET VENT MUST MAINTAIN A MINIMUM 3" CLEARANCE TO ANY COMBUSTIBLE (INSTALL VENT AT CLEARANCES SPECIFIED BY THE VENT MANUFACTURER).

DO NOT CONNECT THE PELLET VENT TO A VENT SERVING ANY OTHER APPLIANCE OR STOVE.

DO NOT INSTALL A FLUE DAMPER IN THE EXHAUST VENTING SYSTEM OF THIS UNIT.

USE AN APPROVED WALL THIMBLE WHEN PASSING THE VENT THROUGH WALLS AND A CEILING SUPPORT/FIRE STOP SPACER WHEN PASSING THE VENT THROUGH CEILINGS (MAKE SURE TO MAINTAIN 3" CLEARANCE TO ANY COMBUSTIBLES.

No more than one tee and 180° of elbows (one tee with two 90° elbows, one tee with one 90° and two 45° elbows, etc.).

33 Feet (max.)

Maximum Venting

Distance

Vent must have a support bracket every 5' of pellet vent when exterior of structure

The vent height and run must not exceed the distance shown in the shaded region shown to the right.

30 Feet

25 Feet

20 Feet

Venting into this shaded area may require restrictor adjustments. See the

15 Feet

section “Restrictor Adjustment” for details.

10 Feet

NOTE: To achieve optimum performance, we recommend keeping the vent as short as possible (horizontal run especially).

0 Feet

5 Feet

 

 

 

 

 

0 Feet

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10Feet (max.)

 

5Feet

 

Travis Industries

4061016

1 0 0 - 0 1 1 8 4

Page 9
Image 9
Lopi Leyden Pellet Stove manual Venting the Pellet Stove, Maximum Venting Distance