Installation Instructions | Section 2 |
|
|
Refrigeration Line Set Installation
GENERAL
Refrigeration line set installations consist of vertical and horizontal line set distances between the ice machine and the condensing unit. The following guidelines, drawings and calculation methods must be followed to assure proper oil return and condensing unit/ice machine operation.
The refrigeration line set installer must be USA
!Warning
Disconnect electrical power to the ice machine head section and the remote condensing unit before proceeding.
A. LINE SET LENGTH
100 feet (30.5 m) Length: The maximum measured length the line set can be.
The receiver is designed to hold a charge sufficient to operate the ice machine in ambient temperatures between
Important
The ice machines will not function with line sets greater than 100 feet (30.5 m). Do not attempt to go beyond this distance and add refrigerant charge to compensate!
B. LINE SET RISE OR DROP
!Warning
The ice machine head section contains refrigerant charge. The ice machine head section contains three
(3)refrigeration valves that must remain closed until proper installation of the line set is completed.
Step 1 Verify Ice Machine and Remote Condensing
Unit Locations Are Within Guidelines.
Prior to installation of the ice machine and remote condensing unit be sure that the distance between then is within the line set routing guidelines outlined in this manual.
Roof/Wall Penetration
If required, cut a
Step 2 Route Refrigeration Tubing
Properly route refrigeration tubing between the ice machine head section and the remote condensing unit.
35’ (10.7 M)
MAX.
DISTANCE
SV1751
35 feet (10.7 m) Rise: The maximum distance the remote condensing unit can be above the ice machine.
15’ (4.5 M)
MAX.
DISTANCE
SV1750
15 feet (4.5 m) Drop: The maximum distance the remote condensing unit can be below the ice machine.
Part Number 000002688 |