Manitowoc Ice QF0800, QF2300, QC0700 Suction Line OIL Traps, Manitowoc S-Trap Kit, Service Loop

Models: QF0400 QC0700 QF0800 QF2300

1 60
Download 60 pages 62.23 Kb
Page 25
Image 25

Section 2

Installation Instructions

 

 

C. SUCTION LINE OIL TRAPS

!Caution

Do not form unwanted traps in refrigeration lines. Never coil excess refrigeration tubing.

0 to 20 feet (0 to 6.1 m) Rise: The ice machine head section has one oil trap built in which allows for a maximum condenser rise of 20 feet (6.1 m) without additional traps in the suction line.

21 to 35 feet (6.4 to 10.7 m) Rise: The suction line requires an additional Oil Trap (“S” type) to be installed. Install the trap as close as possible to midpoint between the ice machine head section and remote condensing unit. S-Trap Kits are available from Manitowoc (refer to chart).

21’ OR MORE

RISE

ADDITIONAL

TRAP KIT

REQUIRED

SV1751

SV1760

Manitowoc S-Trap Kit

Model

S-Trap Kit

Tubing Size

Number

 

 

 

 

 

QF2300

K00166

3/4 inch

(19.1 mm)

 

 

 

 

 

Service Loop

A service loop in the line set permits easy access to the ice machine for cleaning and service.

The supplied service loop is an installation requirement.

A service loop is not considered an oil trap.

The service loop is not included when calculating length, rise or drop of the tubing run.

Do not use hard rigid copper for the service loop.

!Caution

If a line set has a rise followed by a drop, another rise cannot be made. Likewise, if a line set has a drop followed by a rise, another drop cannot be made.

Step 3 Lengthening or Reducing Line Set Lengths

!Caution

Do not form unwanted traps in refrigeration lines. Never coil excess refrigeration tubing.

When the line set required shortening or lengthening, do so before connecting the line set to the ice machine head section or the remote condensing unit.

Continued on Next Page...

Part Number 000002688

2-15

Page 25
Image 25
Manitowoc Ice QF0800 Suction Line OIL Traps, Manitowoc S-Trap Kit, Service Loop, Lengthening or Reducing Line Set Lengths