3. Operation

3.6 Customization of the relay communication card

1.A

1.B

Inputs

Factory setting

-Memorised faults reset command.

-Command to disable transfer.

Signals available on each contact

-Memorised faults reset command.

-Selection command for source S1.

-Selection command for source S2.

-Selection command for the authorised automatic retransfer mode.

-Selection command for the inhibited automatic retransfer mode.

-Command to authorise transfer.

-Command to disable transfer.

-EPO command (enables the opening command for switches Q1 and Q2).

 

Outputs

Factory setting

1.1

 

- Load-supplied status condition (presence or

 

absence of power to the load).

 

 

1.2

 

- General alarm (fault on one of the sources or

 

on the Upsilon STS).

 

 

 

 

 

1.3

 

- Upsilon STS fault.

 

 

 

1.4

 

- Overload status condition.

1.5

 

- Source S1 status condition (active or inactive).

1.6

 

- Source S2 status condition (active or inactive).

 

 

 

Signals available on each contact

-Load-supplied status condition (presence or absence of power to the load).

-General alarm (fault on one of the sources or on the Upsilon STS).

-Upsilon STS fault.

-Source S1 status condition (within or outside tolerances).

-Source S2 status condition (within or outside tolerances).

-Phase-error condition between the two sources (within or outside tolerances).

-Source S1 status condition (active or inactive).

-Source S2 status condition (active or inactive).

-Preferred-source status condition (S1 inactive and S2 active).

-Automatic-transfer status condition (authorised or not).

-Overload status condition.

Page 24 - 34020113EN/AA