4. Maintenance

4.1 Identification of anomalies

General-alarm

S1 31 or S2 32

Static-switch

Buzzer

System output

Meaning

LED 21

LED

LED 33 or 34

 

LED 38

 

 

-

-

Beeps

-

Internal STS fault.

 

 

 

 

 

Source outside

-

 

-

Beeps

-

tolerances, load still

 

 

 

 

 

 

 

 

supplied.

 

 

 

Beeps

 

Source outside

 

 

 

-

 

-

 

-

 

tolerances, no voltage.

 

 

 

 

 

 

 

 

 

 

 

 

 

The load cannot be

 

 

 

 

 

supplied by this source.

 

 

 

Beeps

-

 

-

-

 

 

Static-switch fault.

 

 

 

-

-

-

-

Overload.

-

-

-

-

Load not supplied.

The meaning of all these anomalies are detailed on the display:

Select the alarm: the corresponding informations are displayed.

4.2 Transfer to the manual bypass

Q1

Q5 Q6

Q2

 

 

1

1

4

 

 

 

 

0

0

 

Q1BP

Q3

Q2BP

 

1

1

1

 

0

0

0

 

Q1

Q5 Q6

Q2

 

 

1

1

 

 

0

0

 

 

 

 

6

Q1BP

Q3

Q2BP

 

1

1

1

 

0

0

0

 

Q1

Q5 Q6

Q2

1

 

1

1

 

 

 

0

0

 

 

 

 

7

Q1BP

Q3

Q2BP

 

1

 

1

 

0

0

0

 

Transfer to the manual bypass for source S1:

1 - Manually transfer the load to source S1.

2 - Set switch Q2 4 to the OFF position (position 0).

3 - Set switch Q1BP 6 to the ON position (position 1).

The load is supplied by source S1 via the bypass.

4 - Set switches Q1 1 and Q3 7 to the OFF position (position 0).

The operation for source S2 is identical, using switches Q2 and Q2BP.

Interlocking of the bypass lines is ensured by use of a single key that must be inserted on the bypass switch to be operated.

34020113EN/AA - Page 25

Page 25