6. Appendix

6.1 Technical data Output currents and voltage

Rated output current:

30 A

60 A

100 A

160 A

250 A

400 A

600 A

 

 

 

 

 

 

 

 

 

Input and output voltage:

 

 

 

 

 

 

 

 

Rated operating voltage:

 

 

380 V / 400

V / 415 V

 

 

Maximum voltage:

 

 

498 V (415

V +20%)

 

 

Minimum voltage:

 

 

247 V (380 V -35%)

 

 

Rated frequency:

 

50 or 60 Hz (45 Hz minimum, 66 Hz maximum)

 

 

 

 

 

 

 

 

 

 

Thermal characteristics

Heat losses (1):

 

 

 

 

 

 

 

at rated power:

195 W

295 W

430 W

615 W

920 W

1420 W

2150 W

at 50% rated power:

150 W

195 W

260 W

350 W

495 W

735 W

1070 W

 

 

 

 

 

 

 

 

Required ventilation:

350 m3/h

350 m3/h

350 m3/h

1600 m3/h

1600 m3/h

2300 m3/h

2300 m3/h

 

 

 

 

 

 

 

 

(1) These characteristics are calculated for a voltage of 400 V and a power factor of 0.8.

Noise level

Noise in dB (ISO 3746):

55

55

55

59

59

59

59

Cable sizes

Cross-sectional area in mm2 :

50

50

50

120

120

240

240

Recommended protection devices upstream of Upsilon STS

Type of circuit breaker:

 

 

 

 

 

 

TNS system:

C60L 32A

NS100H 4P 4D

NS160H

NS250H

NS400H

NS630H

 

 

 

4P 4D

4P 4D

4P 4D

4P 4D

TNC system:

 

NS100H 3P

NS160H

NS250H

NS400H

NS630H

 

 

 

3P

3P

3P

3P

 

 

 

 

 

 

 

Trip unit:

curve C

STR22SE

STR22SE

STR22SE

STR23SE

STR23SE

 

 

 

 

 

 

 

Thermal setting:

1.05 In

1.05 In

1.05 In

1.05 In

1,05 In

1.05 In

 

 

 

 

 

 

 

Magnetic setting:

10xIn

10xIn

10xIn

10xIn

10xIn

10xIn

 

 

 

 

 

 

 

Permissible-overload curve

32

In

 

 

 

 

 

16

In

 

 

 

 

 

8

In

 

 

 

 

 

4

In

 

 

 

 

 

2

In

 

 

 

 

 

 

In

 

 

 

 

t(s)

 

0.1 s

1 s

10 s

100 s

1000 s

 

0.01 s

During an overload, transfer between sources is disabled.

Overloads higher than 1.5 In are stored in memory. The alarm must be reset to return to normal operation.