3. Operation

3.5 Upsilon STS customization

1 - Press the menu button 26 .

2 - Select "Setup", then "Customization" using the function buttons 3 - Confirm the order by pressing the function button 23 marked 4 - Enter the password.

23marked ￿ or ￿.

.

The password

Ø

Ø

Ø

is set in the factory.

Select "Setup", then "Password" to personalise the password.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PERSONALIZATION

 

 

 

 

 

Current settings

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Nominal voltage

400 V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Overvoltage threshold

 

10%

 

 

 

 

 

 

 

 

 

 

 

 

Undervoltage threshold

10%

 

 

 

 

 

 

 

 

 

 

 

 

Nominal frequency

50 Hz

 

 

 

 

Overfrequency threshold

5%

 

 

 

 

 

 

 

 

E

 

 

 

Underfrequency threshold

5%

 

 

 

 

 

 

 

 

S

 

 

 

Phase sync tolerance

15°

 

 

 

 

 

 

 

 

C

 

 

 

Retransfer

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The monitoring parameters must be identical for the two sources. These parameters depend on the tolerances of the connected loads.

 

Factory setting

Customization

 

 

 

Return to preferred source after transfer

Automatic

Manual / Automatic

 

 

 

Nominal source voltage

400 V

380 / 400 / 415 V

 

 

 

Overvoltage threshold

Un +10%

Un +5% to Un +20%

 

 

in 1% steps

 

 

 

Undervoltage threshold

Un -10%

Un -5% to Un -20%

 

 

in 1% steps

 

 

 

Nominal source frequency

50 Hz

50 / 60 Hz

 

 

 

Frequency tolerances

± 5%

+1% to +10%

 

 

-1% to -10%

 

 

in 0.5% steps

 

 

 

Phase error tolerance between the two sources

± 15°

± 1° to ± 45° in 1° steps

 

 

 