2.1 Positioning

Upsilon STS 30 - 60 - 100 - 160 - 250 A (cabinet 1400 mm high)

>250 mm

14

15

2. Installation

1 - Unclip the base panels 14 .

2 - Set the cabinet to a level position using the adjustable foot pads 15 .

3 - Put the base panels 14 back in place.

Important: correct ventilation requires at least 250 mm of free space behind the cabinet.

Upsilon STS 30 - 60 - 100 - 160 - 250 - 400 - 600 A (cabinet 1900 mm high)

>350 mm

1 - Unclip the base panels 14 .

2 - Set the cabinet to a level position using the adjustable foot pads 15 .

3 - Put the base panels 14 back in place.

Important: correct ventilation requires at least 350 mm of free space above the cabinet.

14

15

34020113EN/AA - Page 11

Page 11
Image 11
MGE UPS Systems 30A user manual Installation, Positioning