3. Operation

3.3 Normal mode. Operation on preferred source S1

Operation on the preferred source

S1

Q1

S2

Q2

24

29

30

31

32

33

During normal operation on the preferred source S1, LEDs 24 , 29 , 30 , 31 , 32 , 33 , 36 and 38 are on in green.

If LED 38 is orange, there is an overload.

If LED 38 is red, the load is no more supplied.

Q1BP

Q3

Q2BP

36

38

Automatic transfer to the alternate source

S1S2

 

 

24

 

 

29

Q1

Q2

30

 

 

31

 

 

32

 

 

34

Q1BP

Q3

Q2BP

 

 

36

38

The load is automatically transferred to the source offering the highest level of power quality.

For example, if the preferred source S1 goes outside tolerances, LED 31 goes orange or red. The buzzer beeps.

Upsilon STS automatically transfers the load to the alternate source S2. LEDs 24 , 29 , 30 , 32 , 34 , 36 and 38 are on.

Upsilon STS transfers the load back to the preferred source S1 as soon as it returns to within tolerances.

To stop the buzzer, press the

function button marked .

Manual transfer to the alternate source

 

 

25

S1

S2

27

 

 

Q1

Q2

Q1BP

Q3

 

Q2BP

 

 

 

 

 

 

 

 

 

 

 

1 - Press the manual transfer button 25 :

2 - Confirm the order by pressing the grey function button 23 marked on the screen.

LEDs 24 and 27 flash.

After the transfer, the green LED 27 goes on.

The load is supplied by alternate Source 2.

Transfer is authorised only if the two sources are within tolerances (voltage, frequency) and their phase displacement is within the set limits. If these two conditions are not met, the transfer order is stored in memory and executed when the voltages cross zero.

If transfer does not take place within thirty minutes, the order is cancelled.

Page 20 - 34020113EN/AA