Pulsar MX

4.4 UPS Set-Up

Local Settings

Function

Factory Setting

Options

 

 

 

Language

English

French, German, Italian, Portuguese, Spanish

 

 

 

Date/Time Format

International format

US (MM-DD-YYYY/HH:MM AM/PM)

(DD-MM-YYYY/HH :MM)

 

 

 

Date/Time Change

GMT + 1

MM-DD-YYYY/HH :MM adjustable

(Continental Europe)

 

 

 

 

 

Audible Alarm

Yes

No

 

 

 

Output Settings

Function

Factory Setting

Options

Comments

 

 

 

 

Output Voltage

208V

200V / 230V / 220V /

 

240V / 250V

 

 

 

 

 

 

 

 

Freq Converter

Disabled

Enabled

 

 

 

 

 

Output Frequency

60 Hz

50 Hz

User selectable under frequency-

converter mode

 

 

 

 

 

 

 

Eco Mode

Disabled

Enabled

See glossary

 

 

 

 

Slew rate

1 Hz/sec.

0.5 Hz/sec.

 

 

 

 

 

Bypass Transfer

Yes

No

Transfer to bypass if Normal AC

source is out of tolerance

 

 

 

 

 

 

 

 

 

 

Break time calibration during load

Interrupt Time

10 ms

20 ms, ...... , 200 ms

transfer on Normal AC source out

 

 

 

of tolerance

 

 

 

 

Overload Prealarm

105 %

40%, 50%, 70%

Alarm if threshold is overrun

 

 

 

 

ON/OFF Settings

Function

Factory Setting

Options

Comments

 

 

 

 

Cold Start

Disabled

Enabled

Start on battery

 

 

 

 

 

 

 

Enables automatic restart of the

Forced Reboot

Enabled

Enabled

system even if Normal AC source

is restored before the end of the

 

 

 

 

 

 

shutdown sequence

 

 

 

 

Auto Restart

Enabled

Disabled

UPS restarts automatically when

Normal AC source is restored

 

 

 

 

 

 

 

Energy Saving

Disabled

Enabled

Automatic shutdown on battery if

output load level < 10%

 

 

 

 

 

 

 

Sleep Mode

Enabled

Disabled

 

 

 

 

 

 

 

 

Enables consideration of

Remote Command

Enabled

Disabled

shutdown or restart orders from

 

 

 

software to be authorized

 

 

 

 

4 — 2

Access to Maintenance and

86-87050-00 A01

 

Personalization Data

 

Page 28
Image 28
MGE UPS Systems 5000 RT user manual UPS Set-Up, Local Settings, Output Settings, ON/OFF Settings