Installation and User Manual

Battery Settings

Function

Factory Setting

Options

Comments

 

 

 

 

Auto Battery Test

Every week

No test / daily / monthly

 

 

 

 

 

Low Batt warning

20%

0 to 100%

1% increment

 

 

 

 

 

UPS reads number of

 

 

User Battery Settings

battery modules

From 0 to 40 Ah

5 Ah increment

 

connected

 

 

 

 

 

 

Deep Discharge

 

 

Protection against deep

Yes

No

discharge. If disable, MGE UPS

Protect

 

 

SYSTEMS warranty will be void

 

 

 

 

 

 

 

4.5 Maintenance

Function

Sub-Function

Option/Display

Comments

 

 

 

 

 

 

SN: xxxxxxxxx

Serial number

Model

Power Module

SOFT: xxx

Soft version

 

 

NT: xxx

Technical level

 

 

 

 

 

 

Description

10 alarms can be stored

 

Read

Date Hour

Alarm History

automatically

 

Alarm xxx

 

 

 

 

 

 

 

Erase

No / Yes

 

 

 

 

 

Manual Batt Test

Manual Battery Test

No / Yes

 

 

 

 

 

Led & Buzzer Test

Led & Buzzer Test

No / Yes

 

 

 

 

 

Life Cycle Monitoring

LCM

Enable / Disable

Life cycling monitoring alarms

 

 

 

 

 

Auto Statistics

Statistics

You need to register at

Statistics

 

 

www.mgeups.com/Icm to get the

 

Reset Date: No, Yes

Custom Statistics

code and get access to free

 

 

Statistics

statistics

 

 

 

 

 

 

Operation Limits

Operation Limits

 

Automatic alarms displayed when

 

UPS is operating near the limits

 

 

 

 

 

 

 

4.6 UPS Set-Up Using External Software

Insert the Solution-Pac CD-ROM in the drive.

On the first navigation screen, select "Point to Point solution" and follow the instructions on how to install the Personal Solution-Pac software.

Then select "Settings", "Advanced settings" and "UPS settings".

Note: This feature is only supported through Windows and the RS232 communication.

86-87050-00 A01

Access to Maintenance and

4 — 3

 

Personalization Data

 

Page 29
Image 29
MGE UPS Systems 5000 RT user manual Maintenance, UPS Set-Up Using External Software, Battery Settings