MGE UPS Systems 5000 RT user manual Required Protective Devices and Cable Cross-Sections

Models: 5000 RT

1 44
Download 44 pages 52.94 Kb
Page 20
Image 20

Pulsar MX

Remote Power Off communication port (9)

Installation of a Remote Power Off function must be carried out in compliance with applicable regulations.

In order to fully de-energize Pulsar MX RT with the RPO port, it is necessary to use a two-position switch (Normally Open or Closed contact). Once switch is energized/de-energized, the UPS shuts off the display and the output of the UPS.

The output devices can be powered again through auto bypass when the two-position switch is released (open or closed).

The output devices will remain powered < 1 sec. after RPO activation.

Push the start button to return to normal operation.

Note: The internal batteries will remain connected to the power sub-module after RPO activation.

The cable is not included.Remote power off contact normally open (9)

Installation of optional

 

communication card (66102)

RJ12

 

+

5 V DC to 27 V DC

_

Remote power off contact normally closed (9)

RJ12

+

5 VDC to 27 VDC

_

Signal:

activation voltage: 5 V DC to 27 V DC,

current: 10 mA max.

2.6 Required Protective Devices and Cable Cross-Sections

Recommended upstream protection

UPS Power Rating

Upstream Circuit

Breaker

 

5000 RT

D curve - 35A

 

 

2 poles circuit breaker

L1

L2 (N) To UPS Normal AC source

G L2 (N) L1

Required cable cross-sections

Terminal-block cable capacity: 6 mm2, solid or stranded wire (maximum AWG 10).

Capacity for earthing conductor: 6 mm2 , solid or stranded wire (maximum AWG 10).

2 — 6

Installation

86-87050-00 A01

Page 20
Image 20
MGE UPS Systems 5000 RT Required Protective Devices and Cable Cross-Sections, Remote Power Off communication port