3.5 Return to Normal AC Source

After an outage, the UPS restarts automatically when Normal AC source is restored (unless this function has been disabled via UPS personalization) and the load is supplied again.

3.6 UPS Shutdown When AC Present

Before shutdown, please read ALL instructions below:

22

ON AUTO BYPASS

1.Press and hold the "0” (off) button (28) for 3 seconds. The buzzer beeps once.

The load is no longer protected by the UPS. It is powered via the Normal AC source (bypass). If the UPS is set in frequency converter mode, the equipment will not be powered. If the Normal AC source is out of tolerance, the UPS will generate a 10ms output calibrated break.

LEDs (22) is ON, LEDs (33) and (34) are green.

For a full shutdown of UPS and connected load, the upstream circuit breaker (not included) should be set to the off position or remove the Normal AC source.

33

34

28

3.7 UPS Shutdown When on Battery

Before shutdown, please read ALL instructions below:

NO

YES

1.Press and hold the "0” (off) button (28) for 3 seconds. The buzzer beeps once.

2.The display asks for confirmation.

3.Press the scroll button (25) to select yes.

4.Press confirm button (27).

The UPS is now fully shut down.

25

27

28

3 — 4