Troubleshooting

5.1 Troubleshooting LEDS (21) and (22)

5.2 Troubleshooting Not Requiring MGE UPS SYSTEMS After-Sales Support

Press the "Enter" button (27) to display the details below:
Displayed details Signification Correction
NO BATTERY The battery is incorrectly connected Check battery connections (see section 2.9)
I/O BAD CONNECTION AC source is not connected to the
correct terminals Check AC wiring
NO POWER MODULE The power sub-module is not
inserted Check power sub-module connections
(see section 7.1)
NO BATTERYMODULE The battery sub-module is
incorrectly connected Check battery connections (see section 7.2)
INV THERM OVERLOAD The UPS shuts down automatically
because of a major overload Check the power drawn by the connected devices
and disconnect any non-priority devices
INVERTLIMITATION Short circuit conditions on output
devices Check the installation at the UPS output (wiring, fault
equipment)
27
ENVIRONMENT FAULT
If LED (22) is ON:
The equipment is no longer protected by the UPS.
If LED (21) is ON:
The equipment is protected by the UPS but the
operation is downgraded.

Troubleshooting