Troubleshooting

5.1 Troubleshooting LEDS (21) and (22)

If LED (21) is ON:

The equipment is protected by the UPS but the operation is downgraded.

If LED (22) is ON:

The equipment is no longer protected by the UPS.

5.2 Troubleshooting Not Requiring MGE UPS SYSTEMS After-Sales Support

ENVIRONMENT FAULT

27

Press the "Enter" button (27) to display the details below:

Displayed details

Signification

Correction

 

 

 

NO BATTERY

The battery is incorrectly connected

Check battery connections (see section 2.9)

 

 

 

I/O BAD CONNECTION

AC source is not connected to the

Check AC wiring

correct terminals

 

 

 

 

 

NO POWER MODULE

The power sub-module is not

Check power sub-module connections

inserted

(see section 7.1)

 

 

 

 

NO BATTERY MODULE

The battery sub-module is

Check battery connections (see section 7.2)

incorrectly connected

 

 

 

 

 

INV THERM OVERLOAD

The UPS shuts down automatically

Check the power drawn by the connected devices

because of a major overload

and disconnect any non-priority devices

 

 

 

 

INVERT LIMITATION

Short circuit conditions on output

Check the installation at the UPS output (wiring, fault

devices

equipment)

 

 

 

 