2.8 Connection to Output Receptacles2.9 Connection of Extended Battery Module, UPS, and Transformer
1. Check that the battery circuit breaker(s) (13) is OFF ("0" position).
2. Connect the battery power cable (52) to the connector (4) of the power module and to the connector (12) of the battery module.
3. Connect the battery detection cable (53) to the connector (10) of the power module and to the connector (11)of the battery module.
4. Switch on the battery circuit-breaker(s) (13).
TRANSFORMER
INPUT CABLE
BATTERY
MODULE
BATTERY
MODULE
UPS MODULE
Pulsar MX
TRANSFORMER
MODULE
12
13
10
11
4
53
53
53
52
1. Connect the equipment to the UPS 4 NEMAL6-30R.
If more than one load is connected to the
UPS, the total capacity of the loads should
not exceed 30 Amps.
BATT. NO.
200-250V~,24A
RPO
RS-232
CAUTION:
DO NOT DISCONNECT
BATTERY CABLE
UNDER LOAD
BATTERY
CONNECTOR
180VDdc
Pulsar MX
Installation
2 — 8 86-87050-00 A01