4-11. Connecting 1-Phase Input Power For 230 VAC

1

5

=GND/PE Earth Ground

7

4

 

6

 

L1

1

L2

 

2

3

8

 

L2

L1

 

230 VAC, 1

Tools Needed:

YInstallation must meet all National and Local Codes − have only qualified persons make this installation.

YDisconnect and lockout/tagout input power before connecting input conductors from unit.

YAlways connect green or green/ yellow conductor to supply grounding terminal first, and never to a line terminal.

1Black And White Input Conductor (L1 And L2)

2Green Or Green/Yellow Grounding Conductor

3Input Power Cord.

4Disconnect Device (switch shown in the OFF position)

5Disconnect Device Grounding Terminal

6Disconnect Device Line Terminals

Connect green or green/yellow grounding conductor to disconnect device grounding terminal first.

Connect input conductors L1 and L2 to disconnect device line terminals.

7 Over-Current Protection

Select type and size of over-current protection using Section 4-12(fused disconnect switch shown).

8Receptacle (NEMA 6-50R) Customer Supplied

Close and secure door on disconnect device. Remove lockout/tagout device, and place switch in the On position.