4-11. Connecting 1-Phase Input Power For 230 VAC
1
5 | =GND/PE Earth Ground |
7
4 |
| |
6 |
| |
L1 | 1 | |
L2 | ||
|
2
3
8 |
|
L2 | L1 |
| 230 VAC, 1 |
Tools Needed:
YInstallation must meet all National and Local Codes − have only qualified persons make this installation.
YDisconnect and lockout/tagout input power before connecting input conductors from unit.
YAlways connect green or green/ yellow conductor to supply grounding terminal first, and never to a line terminal.
1Black And White Input Conductor (L1 And L2)
2Green Or Green/Yellow Grounding Conductor
3Input Power Cord.
4Disconnect Device (switch shown in the OFF position)
5Disconnect Device Grounding Terminal
6Disconnect Device Line Terminals
Connect green or green/yellow grounding conductor to disconnect device grounding terminal first.
Connect input conductors L1 and L2 to disconnect device line terminals.
7
Select type and size of
8Receptacle (NEMA
Close and secure door on disconnect device. Remove lockout/tagout device, and place switch in the On position.
803