PROTECTIVE FUNCTIONS

 

 

 

 

 

 

Operation Panel

 

Check Point

Remedy

 

Display

 

 

 

 

 

 

 

 

Is the usage frequency of the brake

Reduce the load GD2. Reduce the braking frequency.

 

 

Brake unit

unit appropriate?

Clean the cooling fins.

 

 

cooling fin

Are the cooling fins clogged?

 

 

overheating

Is there any error in the inverter unit

Replace the cooling fan.

 

 

 

cooling fan?

 

 

 

 

 

 

 

 

Control board

Is there an error in the cooling fan?

Replace the cooling fan.

 

 

ambient

Keep the ambient temperature within the

 

 

Is the ambient temperature too

 

 

temperature

specifications.

 

 

high?

 

 

error

 

 

 

 

 

 

 

 

Is there an output short circuit or

Repair the output short circuit and ground fault.

 

 

 

ground fault? (Check the motor

(Repair or replace the motor.)

 

 

 

winding and insulation resistance.)

Lengthen the deceleration time.

 

 

Output over

Was rapid acceleration attempted?

 

 

current

Did the load fluctuate suddenly?

Eliminate the sudden fluctuate in the load.

 

 

 

Was rapid deceleration attempted?

Lengthen the deceleration time.

 

 

 

Were the motor's mechanical

Investigate the braking operation.

 

 

 

brakes applied too quickly?

 

 

 

 

 

 

 

E.15

 

Is the cooling fan's power supply

Repair the short-circuited section.

 

 

Cooling fan

output short circuited?

 

 

 

power supply

Is the cooling fan's power supply

Replace the cooling fan power supply.

 

 

error

abnormal?

 

 

 

 

Is the fuse blown?

Replace the fuse.

 

 

 

 

 

 

 

 

Is the DC circuit short circuited?

Repair the short-circuited section, and replace the DC

 

 

Capacitor

 

fuse.

 

 

Is there an output short circuit or

Repair the output short circuit and ground fault.

 

 

overcurrent

 

 

ground fault? (Check the motor

(Repair or replace the motor.)

 

 

 

 

 

 

winding and insulation resistance.)

 

 

 

 

 

 

 

 

 

Is there an error in the cooling fan?

Replace the cooling fan.

 

 

 

Clean the cooling fins.

 

 

Cooling fin

Are the cooling fins clogged?

 

 

Keep the ambient temperature within the

 

 

overheat

Is the ambient temperature too

 

 

specifications.

 

 

 

high?

 

 

 

 

 

 

 

 

 

 

 

 

Is the gate output short circuited?

Repair the short-circuited section.

 

 

Gate power

Replace the control power supply board.

 

 

Is there an error in the control power

 

 

supply error

 

 

 

supply board?

 

 

 

 

 

 

 

 

 

 

 

zWhen the protective function is activated, take proper corrective action, reset the inverter, then resume operation.

31

Page 42
Image 42
Mitsubishi Electronics FR-A500L instruction manual Check Point Remedy