SPECIFICATIONS

 

 

 

 

Selection can be made from output frequency, motor current (steady or peak value), output

 

Display on

 

Operating

voltage, frequency setting, running speed, motor torque, converter output voltage (steady or

 

 

peak value), electronic overcurrent protection load factor, input power, output power, load

 

operation panel

 

 

 

status

 

 

meter, motor exciting current, cumulative energization time, actual operation time, watt-hour

 

FR-DUO4 or

 

 

 

 

 

 

 

meter, regenerative brake duty and motor load factor.

 

parameter unit

 

 

 

 

 

 

 

 

Display

FR-PU04

 

Alarm

Alarm definition is displayed when protective function is activated. 8 alarm definitions are stored.

 

 

 

 

Operating

Input terminal signal states, output terminal signal states, option fitting status, terminal

 

 

 

definition

(Four alarm definitions are only displayed on the operation panel.)

 

Additional

 

status

assignment status

 

display on

 

Alarm

Output voltage/current/frequency/cumulative energization time

 

parameter unit

 

 

 

definition

 

 

 

 

(FR-PU04)

 

immediately before protective function is activated

 

only

 

 

 

 

 

 

 

Interactive

Operation guide and troubleshooting by help function

 

 

 

 

 

 

guidance

 

 

 

 

 

 

 

 

 

 

Overcurrent shut-off (during acceleration deceleration, constant speed) regenerative

 

 

 

 

overvoltage shut-off, undervoltage, instantaneous power failure, overload shut-off (electronic

Protective/alarm functions

overcurrent

protection), ground fault overcurrent, stall prevention, overload warning, fin

overheat, option error, parameter error, PU disconnection, No. of retries over, output open

 

 

 

 

 

 

 

 

phase, CPU error, 24VDC power supply output short circuit, operation panel power supply short

 

 

 

 

circuit, main circuit error

 

 

 

 

 

 

 

 

Ambient temperature (1)

°

°

 

 

10 C to +40 C (non-freezing)

Environment

 

 

 

 

 

 

Ambient humidity

 

90%RH or less (non-condensing)

 

 

 

 

 

 

 

 

 

 

Storage temperature (2)

°

°

 

 

20 C to +65 C

 

Ambience

 

Indoors. (No corrosive and flammable gases, oil mist, dust and dirt.)

 

 

 

 

 

Altitude, vibration

 

Max. 1000m (3280.80 feet) above sea level, 5.9m/s2 {0.6G} or less (conforms to JIS C 0911)

Note: 1. For FR-A540L-375K, 450K at constant torque (CT) rating maximum ambient temperature can be 50° C (122° F).

2. Temperature applicable for a short period in transit, etc.

43

Page 55
Image 55
Mitsubishi Electronics FR-A500L instruction manual FR-PU04, Alarm