INSTALLATION AND WIRING

(3) Connection of the power supply and motor

Power

R

S

T

<L1>

<L2>

<L3>

supply

 

 

 

Ground

R

S

T

terminal

<L1> <L2> <L3>

No-fuse

 

 

 

breaker

 

 

 

Ground

 

 

U

V

W

 

U

V

W

Motor

 

 

 

Ground

The power supply cables must be

connected to R, S, T<L1, L2, L3>, If they are connected to U, V, W,

the inverter will be damaged.

Connect the motor to U, V, W. In the above connection, turning on the forward rotation switch (signal) rotates the motor in the counterclockwise (arrow) direction when viewed from the load shaft.

(4) Connecting the control circuit to a power supply separately from the main circuit

If the magnetic contactor (MC) in the inverter power supply is opened when the protective circuit is operated, the inverter control circuit power is lost and the alarm output signal cannot be kept on. To keep the alarm signal on terminals R1 and S1 are available. In this case, connect the power supply terminals R1 and S1 <L11 and L21> of the control circuit to the primary side of the MC.

<Connection procedure>

R1 S1 <L11> <L21>

Power supply terminal block for control circuit

R S T

<L1><L2><L3>

MC

Main power supply

Power supply terminal

block for control circuit

1)Loosen the upper screws.

2)Remove the lower screws.

3)Pull out and remove the jumper.

4)Connect the separate power supply cables for control circuit to

upper terminals R1, S1<L11, L21>. (Note 4)

Note: 1. When the main circuit power (R, S, T) <L1, L2, L3,> is on, do not switch off the control power (terminals R1, S1<L11, L21>). Otherwise the inverter may be damaged.

2.When using a separate power supply, the jumpers across R-R1 and S-S1 <L1-L11and L2- L21>must be removed. Otherwise the inverter may be damaged.

3.For a different power supply system which takes the power of the control circuit from other than the primary side of the MC, the voltage should be equal to the main circuit voltage.

4.The power supply cables must not be connected to the lower terminals. If connected, the inverter may be damaged.

11