HDV Series Direct Vent Gas Fireplace | ventING installation |
•The maximum number of 45° elbows permitted per side wall installation is two (2). These elbows can be installed in either the vertical or horizontal run.
•For each 45° elbow installed in the horizontal run, the length of the horizontal run MUST be reduced by 18" (45 cm). This does not apply if the 45° elbows are installed on the vertical part of the vent system.
•The maximum number of elbow degrees in a system is 270°. Figure 24
1 + 2 + 3 + 4 = 270° |
|
|
|
1 |
| 1 |
|
|
|
| |
2 |
| 2 |
|
|
|
| |
3 |
| 3 |
|
|
|
| |
4 |
| 4 |
|
|
|
| |
|
|
| FP1180 |
Example: | Elbow 1 | = | 90° |
| Elbow 2 | = | 45° |
| Elbow 3 | = | 45° |
| Elbow 4 | = | 90° |
Total Angular Variation | = | 270° |
Figure 24 -
Maximum Elbow Usage
Horizontal with vertical rise
1.Locate and cut the vent opening in the wall. For com- bustible walls first frame in opening.
Combustible Interior Walls: Cut a 12Z\x"H x 10Z\x" W hole through the interior wall.
Combustible Exterior Walls: Cut a 10Z\x"H x 10Z\x"W square hole through the exterior wall frame. Figure 25
Noncombustible Walls: Hole opening should be 8Z\x" (216mm) in diameter.
2.The center of the hole should align with the center line of the horizontal rigid vent pipe end. Allow 1/4" minimum rise per foot. Figure 25
10Z\x"
(267 mm)
10Z\x"
(267 mm)
Framing
Combustible Wall
| 8Z\x" |
|
| |||
| (216 mm) |
|
| |||
|
|
|
|
|
| |
|
|
|
|
|
| |
|
|
|
|
|
| |
Figure 25 - | Noncombustible Wall | |||||
|
|
|
|
|
| |
Exterior Wall Framing Dimensions |
20 | 56D3048 |