CLEARANCES | HDV Series Direct Vent Gas Fireplace |
Clearances to combustibles
WARNING
Follow these instructions carefully to ensure safe installation. Failure to follow instructions exactly can create a fire hazard.
The appliance cannot be installed on a carpet, tile or other combustible material other than wood flooring. If installed on carpet or vinyl flooring, the appliance shall be installed on a metal, wood or noncombustible material panel extending full width and depth of the appliance.
Ceiling
72" Minimum
Combustible | Mantel |
|
12" Minimum
12"
Maximum
Depth
| Wall |
|
|
12” |
|
|
|
| 10” |
|
|
12” | 8” |
|
|
6” |
|
| |
|
|
| |
106M” | 4” |
| |
| 956O” |
| 256O” |
| 856M” | ||
|
| 7” | 6” |
Top of
Fireplace
Opening
Insulation Board
Header
Standoffs
FP2282
Side View
Minimum 6"
From Both
Side Walls
Figure 4 -
Clearances from the Mantel, Ceiling, and Side Wall
mantel clearances
FP2282
|
|
| Stud |
|
FP2283 |
|
|
|
|
|
| Wall | Combustible | |
|
| Area | ||
| 1” | 156O” |
|
|
| 256O” | 356O” | 456O” |
|
| 3” |
| 45° | |
Hood |
|
| ||
5” |
|
| ||
|
|
| ||
Side of Fireplace |
|
|
| |
| 6” |
|
| |
Opening |
|
|
|
NOTE: The combustible area around the fireplace must not protrude more than 3/4" from the facing. If it does, it is considered a mantel and must meet the mantel requirements listed in this manual.
Top View
Figure 5 -
Mantel Clearances
WARNING
Never obstruct or modify the air inlet or outlet grilles (louvers). This may create a fire hazard.