Monessen Hearth HDV500NV/PV Venting installation, HDV Series Direct Vent Gas Fireplace, Notice

Models: HDV500NV/PV

1 64
Download 64 pages 30.46 Kb
Page 18
Image 18
Venting installation

HDV Series Direct Vent Gas Fireplace

Vent Cap

HOT

Venting installation

6.Slide the wall thimble over the vent pipe before con- necting the horizontal run to the vent cap. Figure 19

7.Carefully move the fireplace with vent assembly attached toward the wall and insert the vent pipe into the horizontal termination. The pipe overlap should be a minimum of 1Z\v". Apply silicone to the outer pipe connection. Fasten all vent connections with screws provided.

8.Slide the wall thimble against the interior wall surface and attach with screws. Figure 19

FP1955

Apply Mastic to

Figure 17 - All SidesWood Screw

Install Horizontal Vent Cap

Vent Cap (Horizontal Termination)

Interior Wall

Surface

Fire Stop

Assembly

WARNING

Do not recess vent termination into any

 

 

wall. This will cause a fire hazard.

 

Cut Vinyl Siding Away to Fit Standoff

 

or Termination

 

Apply Mastic to All Sides

 

Standoff #1250 or 5DT-VS

 

(Not Required for MHSC

 

Termination)

 

Termination

 

HOT

FP1956

Bolt

Nut

Wood ScrewDo not recess vent termination into any

Figure 18 -

Installing Vinyl Siding Standoff and Termination

NOTICE
Formoreinformation,refertotheinstructions

 

 

supplied with the termination.

 

 

FP1957

 

 

 

Screw

Horizontal

Figure 19 -

Vent Pipe

 

Connect Vent Cap with Horizontal Vent Pipe

Horizontal with vertical rise (through-the-wall) termination configurations

Since it is very important that the venting system main- tain its balance between the combustion air intake and the flue gas exhaust, certain limitations as to vent con- figurations apply and must be strictly adhered to.

The Vent Graph, showing the relationship between vertical and horizontal side wall venting, will help to determine the various dimensions allowable. Page 16

Minimum clearance between vent pipes and combus- tible materials is 3" on top and 1" from bottom and sides unless otherwise noted (Exception: Outside wall with firestop: 1" all around pipes are allowed).

When vent termination exits through foundations less than 20" below siding outcrop, the vent pipe must flush up with the siding.

It is best to locate the fireplace in such a way that minimizes the number of offsets and horizontal vent length.

The horizontal vent run refers to the total length of vent pipe from the flue collar of the fireplace (or the top of the transition elbow) to the face of the outer wall or the mount- ing flange of the termination.

18

56D3048

Page 18
Image 18
Monessen Hearth HDV500NV/PV Venting installation, HDV Series Direct Vent Gas Fireplace, supplied with the termination