FLEX VENT INSTALLATION

WDV Series Gas Fireplace

FLEX VENT INSTALLATION

 

 

2.Install firestop spacers, Figure 26, when penetrating ceiling, attic spaces, or walls.

3.Do not allow the flexible vent to bend in radius tighter than 5" (127 mm). Figure 25

4.Horizontal runs of flexible vent shall be supported at maximum 2 foot intervals; vertical runs, five feet intervals. Metal strapping, properly secured, is an acceptable means to support the flexible vent.

5.Flexible vent spacers are to be installed at intervals prescribed by the flexible vent manufac- turer; and in such a way as to maintain concentric inner and outer vent spacing.

D.Attaching flexible venting to vertical termination assemblies.

1.When using Simpson pipe, an MHSC flex-to-pipe adapter (FPA) and/or rigid pipe section(s) is required to connect the flexible vent assembly to the vertical termination by using three self- penetrating screws.

2.Review Figure 27 and corresponding instructions for proper overlap, clamp and screw place- ment.

3.Three each self-penetrating screws are drilled opposite one another and below the gear clamp.

4.Use only listed and approved terminations and accessories, installed per the installation instruc- tions and Figure 26.

E. Installing flexible venting to horizontal termination assemblies.

1.Connect the 5" flexible vent to the horizontal termination as in Figure 28.

2.Connect the 8" flexible vent to the termination ring as in Figure 28.

3.Review Figure 28 for proper overlap and clamp placement.

4.Three each self-penetrating screws are drilled opposite one another and below the gear lamp.

5.Use only listed an approved terminations and accessories, installed per the termination instruc- tions and Figure 28.

 

 

 

Rigid Pipe Length

 

Termination

Screws

 

 

Cap

 

Flashing

Storm Collar

(3 Places

Flex to Pipe Adapter

equidistant

 

 

 

Roof Support

just above

(FPA/8)

 

gear clamp)

 

Rigid Pipe

 

 

 

 

Gear Clamp

Length

 

 

 

 

 

Flex to Pipe

 

 

1C\v" Flexible Pipe and Adapter

 

 

Outer Collar Overlap

Adapter

 

 

 

 

 

(FPA/8)

 

 

 

 

 

Gear Clamp

UL1777 Flex Vent

 

 

 

 

 

Figure 27 -

 

Firestop

 

Typical Pipe Connection

 

UL1777 Flex

 

 

 

 

MHSC Horizontal

 

PIpe

 

 

 

 

Vent Termination

 

 

Screws

 

 

DVF8A/8

(3 Places equidistant just

 

 

Adapter

above gear clamp)

 

 

UL1777 Flex Vent

 

1C\v" Flexible Pipe and

FP1974

Collar Overlap

 

Gear Clamp

Figure 26 -

Typical Vertical Flex Vent InstallationFigure 28 -

Typical Horizontal Flex Vent Installation

20

78D0011

Page 20
Image 20
Monessen Hearth WDV500 manual WDV Series Gas Fireplace, Flex Vent Installation, 78D0011