WDV Series Gas Fireplace | clearances |
|
|
Clearances to combustibles
WARNING
Follow these instructions carefully to ensure safe installation. Failure to follow instructions exactly can create a fire hazard.
The appliance cannot be installed on a carpet, tile or other combustible material other than wood flooring. If installed on carpet or vinyl flooring, the appliance shall be installed on a metal, wood or noncombustible material panel extending full width and depth of the appliance.
72” Minimum
Ceiling
12” Max.
Depth
|
|
|
|
|
| Wall |
|
|
|
|
|
|
|
|
| ||
| 12" |
|
|
|
|
|
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 6" |
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 21/2" |
|
|
|
|
| |||
| 12" |
|
|
|
|
|
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 9" |
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
| 6" |
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
21/2” Max Depth | Top of Fireplace |
|
|
|
|
|
|
|
|
| |||||||
Opening |
|
|
|
|
|
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Stud
Insulation
Board
Standoff
FP2422
6” Min.
Side View
12” Min.
From Opening
6” Min.
From Opening
Figure 4 - | FP2421 | FP2423 |
| |
Ceiling and Sidewall Clearances | 1” | |||
| ||||
|
|
Side of Fire- |
|
| 256O” | |
| ||||
|
|
|
| |
place Opening |
|
|
| 3” |
|
|
|
Top View
156O”
5”
6”
356O”
456O”
45°
Figure 5 -
Mantel clearances
mantel clearances
NOTE: The combustible area above the facing must not protrude more than 3/4" from the facing. If it does, it is considered a mantel and must meet the mantel requirements listed in this manual.
78D0011